BURNER FLAME CONTROL
SERIES
page 6 di 6
DOUBLE ELECTRODE FLAME DETECTION
IN ACCORDANCE WITH STANDARD EN 298
RETIFICATION OF FAULTS .
? < TROUBLE>
! <CAUSE >
* <REMEDY>
? THE IGNITION SPARK DOES NOT
APPEAR.
! The distance between the electrode and
the burner body is too great.
* Set a distance of max. 2 mm.
! The igniter cable does not make contact
with the pipe.
* re-screw the pipe tightly.
! The igniter cable has a leakage on the
earth.
* Check the laying of the cable, clean the
ignition electrode.
! The ignition voltage is too low.
* use an ignition transformer with power >
5 KV
! The ignition cable is too long.
* Shorten its length to 1 m. (max. 5 m.)
! The igniter cable does not make contact.
* Screw it tightly on the ignition
transformer.
? THE GAS DOES NOT REACH IT
! The gas solenoid valve does not open
* Check the solenoid valve connection.
! There is still presence of air in the gas
hosepipe.
* Make many ignition attempts in order to
fill completely the gas hosepipe.
? THE GAS DOES NOT REACH IT
AND THE IGNITION SPARK DOES
NOT APPEAR, THE
DOES NOT
START.
! Short circuit in the ignition or in the
solenoid valve outlet.
* Check the wiring
- in case of short circuit in outlets
eliminate it and change the inner fuse
(2,5 A). Or send the appliance to the
manufacturer.
? THERE IS THE FLAME BUT THE
DETECTION LED IS OFF.
! The detection electrode is in short
circuit because of dirt, soot or damp.
! The detection electrode is not in a
correct position as to the flame.
! The combustion air/gas ratio is
incorrect.
! The flame makes no contact with the
burner body because air and/or gas
pressure is too high.
! The burner or
are not earthed
correctly.
! Short circuit or detection cable
interruption.
! Phase and neutral wire inverted.
* Eliminate the defect.
? THE APPLIANCE DOES NOT
PERFORM THE IGNITION CYCLE
AND GOES IMMEDIATELY
IN
DETECTION.
! Anomaly on the detection (flame
simulation)
* Eliminate the cause of the flame
anomaly.
! Anomaly of the flame detection circuit.
* Send the appliance to the
manufacturer for its replacement.
? THE APPLIANCE DOES NOT
START EVEN IF ALL THE TROUBLES
HAVE BEEN ELIMINATED AND THE
MAIN SWITCH HAS BEEN PRESSED.
* Send the appliance to the
manufacturer for the functional
inspection.
CAUTION!!!
Danger of death due to shocks!
Before intervening on the appliance cut
off the tension to any cable.
The elimination of breakdowns can be
carried out by authorized personnel
only.
In case of improper repairs or incorrect
electrical connections, the good
running of the appliance is not granted.
The release at distance can be carried
out only by authorized personnel
keeping under strict control the burner
to be lighted