8
24”
FRONT
9” TOP
9”
SIDE
9”
REAR
3. Boiler Location
1. 9” from the top, sides, and rear of the boiler.
2. 18” from the flue pipe in any direction.
3. 24” from the front of the boiler.
The following are the minimum clearances to construction or combustible materials:
DANGER
The boiler must be located on a non-combustible floor. A smooth, level concrete floor
is recommended. Locate the boiler as close as possible to the chimney. If the boiler
is installed on combustible flooring, consult local authorities for proper method of
covering floor. The boiler must not be installed on carpeting.
Caution: Do not store or use flammable materials, chemicals or flammable liquids,
especially gasoline, in the vicinity of this heating appliance.
WARNING
Boiler is certified as an indoor appliance. Do not install boiler outdoors or locate where it
will be exposed to freezing temperatures.
PROVISIONS FOR COMBUSTION AIR AND VENTILATION AIR MUST BE IN ACCORDANCE WITH
SECTION 5.3, “AIR FOR COMBUSTION AND VENTILATION”, OF THE NATIONAL FUEL GAS CODE,
ANSI Z223.1, OR APPLICABLE PROVISIONS OF THE LOCAL BUILDING CODES.
DO NOT INSTALL THE BOILER UNTIL PROPER COMBUSTION AIR HAS BEEN ARRANGED.
The boiler should be installed on a level, flat concrete floor or pad that is structurally sound and
will support the combined weight of the boiler when filled with water. This boiler is designed to
be installed on a noncombustible flooring only. The boiler should be installed as close to the
chimney as possible. Locate the boiler in an area that gives easy access to the rear of the boiler.
To provide good serviceability, the boiler should be installed using minimum recommended
service and accessibility clearances as previously listed in the manual. Under no circumstances
should the unit be installed next to combustible materials with clearances less than listed in
installation clearances in the install manual.
To assemble the two section sets into a boiler block, you will need the tool kit, two clamping
threaded rods, pry bar, a plastic or wooden mallet, nipples, pipe dope and tubes of sealant.