Yes
Yes
No
No
Yes
Saijo denki International co.,ltd.
83
Is there cloging on outdoor
unit heat exchanger ?
Cleaning
Is outdoor unit fan
motor normal ?
Check fan motor
Is there high refrigerant
?
Correct refrigerant amount
Is resistance of
temperature sensor at
outdoor unit heat
exchanger normal?
Chang the sensor
Check the control board
Check code
Check code name
cause
Error 34
Outdoor unit Condenser over
temperature
The outdoor unit heat exchanger temperature is
overheated.