Saijo denki International co.,ltd.
77
Chang the control board
Error 19
Compressor 1 Current sensor fail
There is an error in the dldctric current sensor of
compressor 1
Is the wiring between
compressor 1 and control board
of comoressor normal ?
Correct connection wiring
compressor and control board.
Is the coil resistance of the
compressor 1 normal ?
Change the compressor
Is operation of the
compressor 1 control
board normal ?
check control board
Check code
Check code name
cause