![Saijo Denki CVIA-100-CPF3 Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/saijo-denki/cvia-100-cpf3/cvia-100-cpf3_service-manual_800651078.webp)
No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
71
Check the control board
Error 13
Outdoor unit Ambient Temperature
sensor fail
There is an error in the temper sensor at air inlet
of outdoor unit
Is sensor connect on
control board ?
Correct connector connection
Is the wire of the sensor
normal ?
Change the sensor
Is sensor resistance
normal ?
Change the sensor
Check code
Check code name
cause
Содержание CVIA-100-CPF3
Страница 3: ...Saijo denki International co ltd 2...
Страница 37: ...Models SDV 13M A VTGP1 SDV 60M A VTGP1 Saijo denki International co ltd 35 Wiring Diagrams Indoor unit...
Страница 41: ......
Страница 46: ......
Страница 47: ......
Страница 49: ...Z Service valve Check joint Temperature Saijo denki International co ltd 41 Symbol...