PCD0
Compact RIO’s
Page 20
ã
SAIA-Burgess Controls Ltd.
(HB_PCD0 26 766_E2.DOC)
26/766 E2
RIO 8 I/O DP
Part no.
PCD0.G110
Bus connection
PROFIBUS-DP
DP ID
1635 hex
GSD file
Saia1635.gsd
Number of inputs/outputs
8 combination I/Os which can be used individually as input
or output
Power supply
24V DC ± 20% max. 5% residual ripple
Inputs
Switching level
H level +15V to +30V
L level -30V to +5V
Input current
min. H level (+15V), I >= 3.6mA
max. L level (+5V), I <= 1.2mA
Typical (+24V), I = 6.1mA
Isolation from internal bus
Yes, each channel separately via opto-electronic couplers
Signal delay
2ms typical (hardware)
See also Response Times, page 177.
Outputs
Output current per output max.
1A, overload and short-circuit proof, parallel operation
possible in groups (2 groups: 0-3,4-7)
Total current for whole module max.
4A
Switching level
H level = power supply-0.5V (I
L
< 1A)
L level <= 1V (I
L
= 0A)
Isolation from internal bus
Yes, each channel separately via opto-electronic couplers
Simultaneity
100% @ max. 0.5A per channel
Free-wheeling diode
Integrated
Signal delay
<100µs (hardware)
See also Response Times, page 177.
See also Technical Data, page 162.