6.8
Bus node power consumption
Load of the internal 5V power supply
The bus coupler is supplied with a built-in power supply unit which
provides the internal 5V power supply for the expansion modules from
the 24V power supply.
To determine the load of the internal 5V power supply the maximum
power consumption of every expansion module connected to it must
be added together.
The maximum load of the internal 5V power supply is 5 watts.
If the maximum load is exceeded expansion modules must be
removed from the bus node.
Power consumption of expansion modules from the internal
5V power supply (maximum values)
RIO 16 I
0.275W
RIO 4 I 120 VAC
0.2W
RIO 4 I 230 VAC
0.2W
RIO 16 O
0.325W
RIO 4 O R
0.25W
RIO 8 I/O
0.325W
RIO 8 I 8 I/O
0.325W
RIO 4AI ±10V
0.325W
RIO 4AI/4AO ±10V
0.325W
RIO 4AI 20mA
0.325W
RIO 4AI/4AO 20mA
0.325W
RIO 4AI 4-20mA
0.325W
RIO 4AI/4AO 4-20mA
0.325W
RIO T10-10
0.325W
RIO T20-10
0.325W
RIO C24-10
1.1W
RIO P24-10
1.25W