SE_20200507_HTE 400_M
10
HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed
DIMENSIONS OF RELEASE SYSTEMS WITH CO
2
H [mm]
150
>150
150
200
250
300
350
400
≥ 450
25
0
150
125
100
75
50
25
0
5
Yinf [mm]
Ysup [mm]
BOc [mm]
1.5
HTE 400 + CO
2
DRIVEN RELEASE- Confi guration G0
CONFIGURATION
• G0 - CO
2
Driven release
2 Micro FD 531
FAIL-CLOSE LOGIC
- Working conditions /
torsion spring loaded / lever in horizontal position / piston not powered
Î
DAMPER OPEN
- Normal conditions or failure /
torsion spring unloaded / lever in vertical position / CO
2
release at piston
Î
DAMPER CLOSED
W [± 2 int.]
36
36
180
MS
H [± 2 int.]
36
36
Y
sup.
Y
inf.
H + 68
400 [± 5 ext.]
165
125
Wall limit
165
70
BO
BO
BO
c
The dimensions shown on all diagrams are expressed in [mm]
MS
= Minimum space for servicing servo motor/mechanism 200 mm
BO
= Blade overhang
For dampers with height > 400 mm blade overhang is:
H - 400 mm
2