Configuring Wiegand vs. Data clock
Configuring Wiegand vs. Dataclock
MorphoAccess is configured during manufacturing to support
the Wiegand protocol. If your installation requires supporting
the Dataclock protocol, you will need to perform the following
procedure in order to configure the device to support Dataclock.
You will be taking the housing sections apart and then putting them
back together again in order to perform the configuration.
Note:
MorphoAccess can support either Wiegand or
Dataclock. MorphoAccess does NOT support both protocols
simultaneously.
Note:
This installation requires the device to be disconnected
from the mounting surface with the main power to the device
turned off.
Performing the Configuration
1. Remove the four visor screw caps and the four screws securing
the visor and remove the visor.
2. Unscrew the front housing from the back housing by removing
the four screws securing the two halves together.
3. Carefully separate the front and rear housing.
Note:
Carefully disconnect the cables between the front and
rear housing before completely separating the two halves.
4. Turn the front housing upside down in order to look inside.
Identify the location of the bank of eight vertical jumpers on the
motherboard by looking at the picture on the next page.
Содержание MorphoAccess 200E
Страница 1: ......
Страница 2: ......
Страница 4: ...ii ...
Страница 9: ...5 General description Rear View Wiegand RS 485 Power Ethernet Multi function Wall Gasket Location ...
Страница 29: ...25 Appendix 1 Rear View Location of Cables Multi function Ethernet Power Wiegand RS485 ...
Страница 34: ......
Страница 35: ......
Страница 44: ......
Страница 45: ......
Страница 47: ......
Страница 111: ......
Страница 112: ......