Step-by-Step Procedure for Step 3 

a) 

Enter the drive Operating Mode in parameter 0-00. 

 

0-00 = 0000 Vector (General Purpose) “Default Setting”. 

 

0-00 = 0001 Vector (Variable Torque). 

 

0-00 = 0002 Volts / Hz. 

b) 

If a value of 0002 (Volts/Hz) was entered for parameter 0-00, then skip to step K. 

c) 

Enter Motor Rated Voltage from motor nameplate in parameter 0-01. 

d) 

Enter Motor Rated Current from motor nameplate in parameter 0-02. 

e) 

Enter Motor Rated Kilowatts (kW=HPx.746) from motor nameplate in parameter 0-03. 

f) 

Enter Motor Rated Speed (RPM) from motor nameplate in parameter 0-04. 

g) 

Enter Motor Rated Frequency from motor nameplate in parameter 0-05. 

h) 

Set parameter 0-06 equal to 0001 (enable auto tuning). Press the 

 key and the auto tuning 

function will start and the display will read " - At -".   

i) 

The motor will not rotate during the auto tuning process but voltage will be applied to the motor. 

j) 

When the auto tuning is successful, the display will read parameter 0-06. Otherwise an auto 

tuning error will be displayed. Press the 

 key until the display reads "5.00" (frequency 

reference). Setup is completed. Skip the remaining steps K through O). 

k) 

For Volts / Hz Operation, Select a pattern in parameter 10-0 = 0-18 (See page 73-75 of the 
instruction manual for more detailed information) each pattern selects default values for 
parameters 10 - 1 through 10-9. These values may require tuning to meet your application speed 
and torque requirements. 

l) 

Parameter 10-0 = 18, allows for a custom Volts/Hz pattern to be entered in parameters 10-4 to 
10-9 to meet specific applications. Refer to page 73 of the instruction manual.   

m) 

If the motor rated frequency is not 50 or 60 Hertz, adjust parameter 10 - 4 to the desired motor 
rated frequency. 

n) 

If you wish to operate the motor at a frequency higher than the motor rated frequency, adjust 
parameter 3-00 to the maximum frequency desired. 

o) Press 

the 

 key until the display reads "5.00" (frequency reference). Setup is now 

completed. 

 
 

Step 4 Check Motor Rotation 

  

 

Press RUN key (FWD LED should light), motor should start running, and the digital operator should 

display a value increasing from 00.00 to 05.00.  

• 

Check Motor Rotation.

 

If the motor does not rotate in the correct direction: 
Press STOP key. Remove AC power. Wait for LED "charge" lamp to extinguish. 
Reverse motor leads T1 and T2. Restart the drive and check the rotation. 

  

Press STOP key to stop the drive.

 

Содержание CV10

Страница 1: ...CV10 Compact Vector AC Drive Quick Start Guide REV 1 1 PART NUMBER 027 2177 SEPTEMBER 2004...

Страница 2: ...cription of Main Circuit Terminals 4 Description of Control Circuit Terminals 4 Keypad and Display Description 5 Step 2 Apply Power to the Drive 5 Parameter Groups 6 To Change Parameter Data 6 Step 3...

Страница 3: ...Installation on pages 18 through 32 If you feel this was abnormal do not start the drive until qualified personnel have corrected the situation Failure to do so could result in serious injury Check Dr...

Страница 4: ...ignal SW 1 NPN PNP selective 10V COM AIN R1A R1B R1C R2A R2B SW 1 NPN PNP CON2 RS485 RS232 Memory Card Option Card DC reactor Braking Resistor note1 Molded case circuit breaker Magnetic contactor AC P...

Страница 5: ...ormally close contact R1A Normally open contact Multifunctional terminals Normally open Contact rated capacity 250VAC 1A or 30VDC 1A Contact using description refer to 8 02 8 03 10V Speed Potentiomete...

Страница 6: ...f stopped Stays Lit while operating 9 DSP FUNC Access program mode Scroll thru monitoring functions 10 LOCAL REMOTE Switches between Local Keypad Operation and Remote Control Terminal Control 11 LCD k...

Страница 7: ...nal Operation 9 Drive and Load Protection Modes 10 Volts Hz Pattern Operation Mode 11 PID Operation Mode 12 PID Limits and Out of Range Mode 13 Communication Mode 14 Motor Auto Tuning Parameters 15 Dr...

Страница 8: ...the motor varies and fast response of the drive to motor speed command changes is not required Can only be used when a single motor is connected to the drive Fans and pumps c Volts Hz Use for multiple...

Страница 9: ...Setup is completed Skip the remaining steps K through O k For Volts Hz Operation Select a pattern in parameter 10 0 0 18 See page 73 75 of the instruction manual for more detailed information each pa...

Страница 10: ...set greater than the Motor Rated Frequency parameter 0 05 for vector modes parameter 10 4 for Volts Hz mode the motor will operate in the constant horsepower mode when motor rated frequency is exceede...

Страница 11: ...put External 0 10V or 0 20 mA Signal 100 0 Figure 1 Set SW2 switch per Table 1 based on the type of analog signal connected to the drive use 0 10 VDC position for potentiometer input Type of external...

Страница 12: ...ed to use the keypad pushbuttons to start and stop the drive To enable starting and stopping the drive using external switches or pushbuttons set parameter 1 00 equal to 0001 External Terminal Control...

Страница 13: ...top Forward Reverse a Input signal is NPN Active Low b Input Signal is PNP Active High S1 Run Stop S2 Fwd Rev COM Common S1 Run Stop S2 Fwd Rev 24V Common Figure 3 B Functions of Digital Inputs S1 and...

Отзывы: