CV10

 

Quick Start Guide

 

 

 

 

 
SEPTEMBER 2004  

 

11 

 

 
4) 

Parameter 1-06 = 0003: The Up/Down Digital Inputs (Digital Input Function Codes 14 and 15) set 

the Frequency Command. Set Parameters 5-03 to 0014 and 5-04 to 0015 and connect Up 

/ Down 

pushbuttons to the drive as shown below in Fig 2. 
 

S4    Up

S5   Down

COM   Common

24V   Common

S4    Up

S5   Down

NPN Inputs

(sink)

PNP Inputs

(source)

 

Figure 2 

 
5) 

Parameter 1 - 06 = 0004: Serial Communications set the Frequency Command. Refer to the 

serial communications document for more detailed information. 

h) 

Set for External Start / Stop Control:

 By default, the drive is configured to use the keypad 

pushbuttons to start and stop the drive. To enable starting and stopping the drive using external switches 
or pushbuttons, set parameter 1-00 equal to 0001 (External Terminal Control) and set parameter 1 - 01 
to the desired value as described below. After setting parameters 1-00 and 1-01, remove AC input 
power,  wait for the "Charged" LED to extinguish, and connect the switches or pushbuttons as shown in 
Figures 3-A, 3-B, and 3-C. Reference page 52 of the CV10 instruction manual for more detailed 
information. 
 

Set Switch SW1 according to the desired type of digital input used: 
 

SW1 

Type of external signal 

Remarks 

 

         N      NPN 

 
 
 

NPN input (sink) 

(Zero volts on the input terminal is ON) 

Active Low 

 
 
                   
            
                      PNP 
 
 
 

PNP input (source) 

(24 VDC on the input terminal is ON) 

Active High 

 

Factory 

default 

 

 

 

 

 

Содержание CV10

Страница 1: ...CV10 Compact Vector AC Drive Quick Start Guide REV 1 1 PART NUMBER 027 2177 SEPTEMBER 2004...

Страница 2: ...cription of Main Circuit Terminals 4 Description of Control Circuit Terminals 4 Keypad and Display Description 5 Step 2 Apply Power to the Drive 5 Parameter Groups 6 To Change Parameter Data 6 Step 3...

Страница 3: ...Installation on pages 18 through 32 If you feel this was abnormal do not start the drive until qualified personnel have corrected the situation Failure to do so could result in serious injury Check Dr...

Страница 4: ...ignal SW 1 NPN PNP selective 10V COM AIN R1A R1B R1C R2A R2B SW 1 NPN PNP CON2 RS485 RS232 Memory Card Option Card DC reactor Braking Resistor note1 Molded case circuit breaker Magnetic contactor AC P...

Страница 5: ...ormally close contact R1A Normally open contact Multifunctional terminals Normally open Contact rated capacity 250VAC 1A or 30VDC 1A Contact using description refer to 8 02 8 03 10V Speed Potentiomete...

Страница 6: ...f stopped Stays Lit while operating 9 DSP FUNC Access program mode Scroll thru monitoring functions 10 LOCAL REMOTE Switches between Local Keypad Operation and Remote Control Terminal Control 11 LCD k...

Страница 7: ...nal Operation 9 Drive and Load Protection Modes 10 Volts Hz Pattern Operation Mode 11 PID Operation Mode 12 PID Limits and Out of Range Mode 13 Communication Mode 14 Motor Auto Tuning Parameters 15 Dr...

Страница 8: ...the motor varies and fast response of the drive to motor speed command changes is not required Can only be used when a single motor is connected to the drive Fans and pumps c Volts Hz Use for multiple...

Страница 9: ...Setup is completed Skip the remaining steps K through O k For Volts Hz Operation Select a pattern in parameter 10 0 0 18 See page 73 75 of the instruction manual for more detailed information each pa...

Страница 10: ...set greater than the Motor Rated Frequency parameter 0 05 for vector modes parameter 10 4 for Volts Hz mode the motor will operate in the constant horsepower mode when motor rated frequency is exceede...

Страница 11: ...put External 0 10V or 0 20 mA Signal 100 0 Figure 1 Set SW2 switch per Table 1 based on the type of analog signal connected to the drive use 0 10 VDC position for potentiometer input Type of external...

Страница 12: ...ed to use the keypad pushbuttons to start and stop the drive To enable starting and stopping the drive using external switches or pushbuttons set parameter 1 00 equal to 0001 External Terminal Control...

Страница 13: ...top Forward Reverse a Input signal is NPN Active Low b Input Signal is PNP Active High S1 Run Stop S2 Fwd Rev COM Common S1 Run Stop S2 Fwd Rev 24V Common Figure 3 B Functions of Digital Inputs S1 and...

Отзывы: