CV10
Quick Start Guide
SEPTEMBER 2004
12
1. Parameter 1-01 = 0000: Forward/Stop - Reverse/Stop
a. Input signal is NPN (Active Low) b. Input Signal is PNP (Active High)
S1 Forward
S2 Reverse
COM Common
S1 Forward
S2 Reverse
S1 Forward
S2 Reverse
24V Common
Figure 3-A
If both forward and reverse commands are applied at the same time, the drive will stop. Functions of
Digital Inputs S1 and S2 are overridden by this command.
2. Parameter 1-01 = 0001: Run/Stop - Forward/Reverse
a. Input signal is NPN (Active Low)
b. Input Signal is PNP (Active High)
S1 Run/Stop
S2 Fwd/Rev
COM Common
S1 Run/Stop
S2 Fwd/Rev
24V Common
Figure 3-B
Functions of Digital Inputs S1 and S2 are overridden by this command.
3. Parameter 1-01 = 0002: 3 Wire Control Mode, Run/Stop - Forward/Reverse
a. Input signal is NPN (Active Low)
b. Input Signal is PNP (Active High)
S1 Run
S2 Stop
COM Common
S3 Fwd/Rev
S1 Run
S2 Stop
24V Common
S3 Fwd/Rev
Figure 3-C
Functions of Digital Inputs S1, S2, and S3 are overridden by this command.
Note: If parameter 1-02 = 0001, then the reverse commands in all of the above figures will act like
a stop command.