Step 5 Check Full Speed at 50Hz/60Hz
•
Frequency/Speed can be changed by pressing the
or
keys. To move left for
next digit, press
key. Press the
key to set the speed.
•
Set frequency to 50Hz/60Hz as applicable.
•
Press RUN key and check drive acceleration to full speed.
•
Press STOP key to stop drive and check deceleration.
•
Display should now read the last set frequency.
Step 6 Other Operations
The drive is now setup for basic Run/Stop operation in both forward and reverse directions from the
keypad. For other motor control options see below.
a)
Disable Reverse Operation:
Set parameter 1-02 equal to 0001 to disable reverse operation.
When set, the FWD/REV button on the keypad will no longer function and any external reverse
commands will stop the motor. Refer to page 53 of the instruction manual.
b) Change
Acceleration
Time:
Parameter 3-02 sets the acceleration time in seconds.
Acceleration Time is defined as the length of time to accelerate the motor from zero speed to Motor
Rated Speed. Refer to page 56 of the instruction manual.
c)
Change Deceleration Time:
Parameter 3-03 sets the deceleration time in seconds. Deceleration
Time is defined as the length of time to decelerate the motor from Motor Rated Speed to zero
speed. Refer to page 56 of the instruction manual.
d)
Set Maximum Speed:
Parameter 3-00 sets the maximum output frequency to the motor. If
Parameter 3-00 is set greater than the Motor Rated Frequency (parameter 0-05 for vector modes,
parameter 10-4 for Volts/Hz mode), the motor will operate in the constant horsepower mode when
motor rated frequency is exceeded. Refer to pages 51, 56 and 73 of the instruction manual.
e)
Set Minimum Speed:
Parameter 3-01 sets the minimum output frequency to the motor. Refer to
page 56 of the instruction manual.
f)
Local / Remote Selection:
By default, the drive is configured to use the UP/DOWN keys on the
keypad (Local Control) to set the Frequency Reference (motor speed command) for the drive and
the RUN/STOP key to control the starting and stopping of the motor (Local Control). Once
parameters 1-00 and 1-06 are set to any value other than 0000, the drive recognizes it as
REMOTE CONTROL. By pressing the RESET and FWD/REV keys simultaneously the drive
switches between LOCAL CONTOL and REMOTE CONTROL or vice versa.
Note: Parameter 1-00 and 1-06 must be set to remote in order for this function to take
effect.
g)
Set Frequency Reference Source
: Change parameter 1-06 to change the frequency reference
source as shown below. After setting parameter 1-06, remove AC input power, wait for the
"Charged" LED to extinguish, and connect any devices to the drive as shown in Fig. 1. Reference
to page 53 of the instruction manual.
1)
Parameter 1-06 = 0000: The Up/Down Arrow Keys on the keypad set the Frequency
Reference Command.
Default Setting
.
2)
Parameter 1-06 = 0001: The Potentiometer Mounted on the Keypad sets the Frequency
Reference Command.
3)
Parameter 1-06 = 0002: The Analog Voltage/Current connected to Terminal AIN sets the
Frequency Reference Command.