SDC-620 Multiple door controller
11
Product specifications
Copyright© 2016
– Saflec Systems (Pty) Ltd.
http://www.saflecsystems.co.za
PRODUCT SPECIFICATIONS
Power requirements
Operating Voltage (DC)
10 to 14 Vdc
Maximum Current
300 mA
Maximum Current (Including two
SSR-201 proximity card readers)
500 mA
Environmental characteristics
Operating Temperature
0°C to +70°C
Storage Temperature
-10°C to +80°C
Enclosure Rating
IP54
Inputs
Input Type
Digital
Typical Input Voltage (Internal Mode)
0 to +12Vdc
Maximum Input Voltage
-12 to 36Vdc
Maximum Input Current
7.3 mA
Outputs
Output type
Relay
– internally powered or potential free contact
Maximum voltage (AC)
250Vac
Maximum voltage (DC)
220Vdc
Internally powered Outputs
Maximum combined current
3.7A
Recommended maximums per relay
750mA at 12Vdc
Externally powered Outputs
Recommended current (DC)
2A at 30Vdc
Recommended current (AC)
1A at 125Vac
Note:
Care must be taken not to exceed the contact ratings listed to prevent damage to the controller.
RS-485 controller network
Transient Protection
Yes
Protection type
Galvanic isolation
Maximum protection voltage
2kV
Maximum Network Length
1000 metres
RS-485 reader network
Transient Protection
Yes
Protection type
Galvanic isolation
Maximum protection voltage
2kV
Maximum Network Length
500 metres (Data only)
RS-232 Host Interface
Transient Protection
No
Maximum Cable Length
15 metres
Auxiliary power output
Voltage (DC)
12Vdc
Total output current
3A