background image

SDC-620 Multiple door controller 

 

 

 
Copyright© 2016 

– Saflec Systems (Pty) Ltd. 

http://www.saflecsystems.co.za 

NOTE:

 The power supplied by the controller is dependant on the length of the cable and the 

number of readers being supplied with power. Should the cable length be too long, or should there 
be too many readers the voltage drop might cause the power to be insufficient. 
 
The devices do not have to be powered from the controller. They can also be powered individually 
from a separate power supply, should this be preferable, however best practice would be to strap 
the ground of the external power supply to the ground on the controller as per the previous 
diagram to prevent issues with a ground potential difference. 

Step 5a: (Optional) Connect the Ethernet Host interface 

One of the controllers on the RS-485 controller network has to be connected to the PC for the 
device network to be able to communicate with the host system. This can be done through either 
the Ethernet connection or the RS-232 connection. 
The Ethernet cable is a non-

‘power over Ethernet’ cable to an RJ-45 plug. The typical wiring used 

for the Cat5 cable that is used for this connector is the ‘T-586B’ wiring scheme as seen in the 
figure below. 

 

 
 
 
 
 
Figure 7 

Wiring used in the RJ-45 plug as seen from below. 

 
Configure the network configuration for the controller using the diagnostics panel: 

 

Browse the menu to the page entitled ‘IP Address’ 

 

Press ‘Enter’ to edit the address 

  Using the Right and Left buttons select the part of the ad

dress that you’d like to change. 

The part will be highlighted as in the figure below. 

  Use the Up and Down buttons to increase or decrease the number at that position. Holding 

the button down will speed up the change. 

 

 

 

Figure 8 

The pages as seen during configuration. 
 

  Repeat the above process for the 

‘Subnet Mask’ and ‘Gateway’ settings. 

 

Once you’ve set everything correctly, browse through the pages until you get to a page 
entitled ‘Save Settings’. Press Enter to apply the change then reboot the controller. 

 

Содержание SDC-620

Страница 1: ...ked using a protected RS 485 network The PC can connect to it using either RS 232 or the built in Ethernet connector or through the RS 485 network from another controller It has a reader RS 485 networ...

Страница 2: ...SDC 620 Wiegand door controller 2 Copyright 2016 Saflec Systems Pty Ltd http www saflecsystems co za Figure 2 Possible position for an SDC 620 in a SACS access control system...

Страница 3: ...wer the panel will be active If the screen is blank it will be in screen saving mode Tapping any button will awaken the screen and allow you to configure the device Figure 3 The configuration and diag...

Страница 4: ...ations network Each controller on this network requires a unique address for communications and identification Duplicate addresses will cause communication problems The address of the controller can b...

Страница 5: ...n the line by shorting J6 Controllers in the middle of the line must not have the termination jumper inserted as this can cause network problems In the diagram above you will see that the controller o...

Страница 6: ...mmunicate with the host system This can be done through either the Ethernet connection or the RS 232 connection The Ethernet cable is a non power over Ethernet cable to an RJ 45 plug The typical wirin...

Страница 7: ...oard with the power connector on the top right of the board the inputs are arranged in ascending order from left to right with a shared common between each input pair See the diagram below on how to c...

Страница 8: ...for the output relays Figure 12 Example wiring for an externally powered magnetic lock Normally closed Output mode 2 Internally powered outputs To set the output to internally powered mode place two j...

Страница 9: ...gand devices communicate with the SDC 620 via five signalling lines These lines can be broken into two groups The data lines Data 0 Data 1 The control lines Red LED Green LED and Buzzer Note Make sure...

Страница 10: ...interface front page It shows basic diagnostics information on the main page but the links at the bottom will require a username and password for authentication The default username is root and passwo...

Страница 11: ...contact Maximum voltage AC 250Vac Maximum voltage DC 220Vdc Internally powered Outputs Maximum combined current 3 7A Recommended maximums per relay 750mA at 12Vdc Externally powered Outputs Recommende...

Страница 12: ...SDC 620 Multiple door controller 12 Copyright 2016 Saflec Systems Pty Ltd http www saflecsystems co za Notes...

Отзывы: