11
SL2 v. 2.01 EN
Configuration
PROGRAMMING DATA
CODE DATA
COMMENTS
Enter programming mode
00
Enter password
* - - - - #
Default = 0000
Exit programming mode
*00*#
ALARM CODES
CODE DATA
COMMENTS
P100 ID code
*01*
- - - - - - - - #
P100 is always 8 digits
CPC ID code
*02*
- - - - - - #
CPC 6-8 digits
Q23 ID code
*03*
- - - - - - - - - - - - # Q23 is always 12 digits
TELEPHONE NUMBERS
CODE DATA
COMMENTS
1st Phone number
*11*
- - - - - - - - - #
Phone number to alarm receiver 0-16 digits.
If calling through a switch board, delay time
can be set by adding asterisks between
leading number of the switchboard and tele-
phone number for the alarm call receiver.
Each asterisk is equal to one second delay.
Example: *11*(0)**1234567#
2nd Phone number
*12*
- - - - - - - - - #
3rd Phone number
*13*
- - - - - - - - - #
4th Phone number
*14*
- - - - - - - - - #
CALL TYPE
CODE DATA
COMMENTS
Call type 1st number
*21*
- #
Change the call type for the telephone
numbers stored.
0 = P100
1 = VOICE (Default)
2 = Q23
3 = CPC
Change this only if your alarm operator is
using any of the mentioned protocols.
Call type 2nd number
*22*
- #
Call type 3rd number
*23*
- #
Call type 4th number
*24*
- #
Call type LMS number
*30*
- #
LMS (Lift Monitoring System) call type
0 = P100
3 = CPC (Only battery alarm)
4 = Caller ID (Battery powered only)
TEST ALARM/BATTERY ALARM CODE DATA
COMMENTS
LMS phone number
*16*
- - - - - - - - - #
LMS (Lift Monitoring System) phone number
to alarm receiver/SLCC.
Test alarm
*17*
- - - - - - - - - #
Phone number to test alarm receiver/SLCC.
Days between tests
*27*
- - #
Number of days between test alarms, 00-99
days. Always two digits. Max 3 days accord-
ing to EN 81-28.
00 = No test alarms
Test alarm protocol
*31*
- #
Protocol test alarm
0 = P100
3 = CPC
4 = Phone number used as ID.
ALARM CHARACTER
CODE DATA
COMMENTS
Alarm character 1st number
*41*
- - #
Alarm character. only when using CPC as
alarm protocol normally 10 or 27 check with
your alarm company !
Alarm character 2nd number *42*
- - #
Alarm character 3rd number *43*
- - #
Alarm character 4th number
*44*
- - #
Alarm character LMS
*45*
- - #
LMS (Lift Monitoring System) (Battery alarm)
Normally 17
Alarm character Test alarm
*46*
- - #
Normally 26
Parameter List