Power-Fill System
Provide adequate electrical power (41 amps @13.5V DC, 21 amps @ 27V DC) from the battery. Use 8
AWG wire directly from the battery or battery switch. Long wire runs will require a larger gauge wire for
proper operation. Use the following as guidelines for longer wire runs.
Electrical devices can be easily damaged by a weak or erratic power supply. The Power-Fill system is no
different - the better the power supply, the better the system will perform.
DO NOT
connect the main power to leads that supply power to some other device, such as a light bar,
siren, or primer pump.
Do not attach the red power wire to the hot side of the solenoid. Power and
ground for the controller needs to come from a separate power source
.
NOTE: Any system without a flow switch will require Jumper 2520-0118 or system will shut down
automatically after 20 seconds.
Wire Size
Wire Length
8 AWG
10 feet or less
6 AWG
10-20 feet
4 AWG
20 feet or more
DC Truck-Mounted System
Battery
Control Panel
Male Connector
with Female Pins
Female Connector
with Male Pins
Black
Red
Flow Switch
Float Switch
14 AWG
8 AWG
14 AWG
Brown
Battery
Power Solenoid
Pump/Motor Assy.
Negative Motor Lead
8 Ga Wire
Positive Motor Lead
8 Ga Wire
Three Pin
Connector
To ground or
negative side
of battery
Green wires
Blue wires
Do not attach the red
power wire to the hot
side of the solenoid.
Power and ground for
the controller needs to
come from a separate
power source.