Normal start-up procedure
.
2. Confirm that the system conditions permit the compressor to start.
3. Press the start button.
4. Allow the compressor to start up and stabilise.
5. Observe the compressor unit for mechanical tightness of the external piping, bolts, and
valves. Ensure that the unit is clean from oil and refrigerant leaks. If not satisfactory, shut
down the compressor and correct the problem using good safety precautions.
Restarting the compressor unit after control power interruption, plant power
failure
1. Check variable set points.
2. Follow normal start-up procedure.
Stopping routine
Brief stop
You can stop the compressor at any capacity setting. However, under normal conditions it is
recommended to reduce the capacity to a minimum before you stop the compressor.
Leave all valves in their in-operation positions. Do not turn off the power to the screw compressor
unit as the oil heater must be connected to keep the correct oil temperature.
Shut down for long periods
Before you begin:
• To perform servicing and repair work, you must close the necessary valves
• To reduce the risk of bearing damage, it is recommended to rotate (to a new position) the
motor and compressor on a monthly basis. If the screw compressor unit is exposed to
vibrations during a long shutdown period, the interval should be changed to weekly.
• Avoid high vibration levels.
1. Complete the procedures in
.
2. Disconnect the oil heater.
3. Close the suction and discharge valve.
Long term storage
Long term storage (6 months to 5 years) provisions are required, regardless of the storage
environment, if start-up and/or useful operation does not take place within six (6) months of
equipment shipment. Special provisions may be required for storage of less than six (6) months
if the storage area is subject to unusual environments such as high humidity, large temperature
changes, or dusty atmosphere.
Long terms torage of equipment may lead to the deterioration of components over the period
of time. Synthetic components in the compressor may deteriorate over time even if they are kept
flooded with oil. A warm and dry environment is essential to minimise environmental and corrosive
damage.
For further information, contact Johnson Controls Denmark.
SAB 283-355 A-Frame OHU 6042 and OHU 7650 (including ATEX) Screw Compressor Unit