Areas of application of the screw compressor
You must adhere to the following application of the screw compressor and application of
combustion engine guidelines.
Application of the screw compressor
To prevent unintentional application of the compressor, which could injure personnel or damage
equipment, you must observe the following guidelines:
• You must only use the compressor as a refrigeration compressor and within the operating limits
specified in the manuals or in a written agreement with Johnson Controls Denmark.
• You must only use the compressor with the refrigerant(s) and number of revolutions per
minute, as shown on the compressor name plate. You must only use other refrigerants in
accordance with Johnson Controls Denmark's instructions. You must only use all other types of
gas with written permission from Johnson Controls Denmark.
• Johnson Controls Denmark further accept no liability of any kind for damage to the compressor
unit and plant parts caused by torsional oscillation, or the like, which is attributable to built-in
VSD solutions initiated by the customer after delivery.
•
ATEX
: The compressor is approved for application in potentially explosive atmospheres
provided it is fitted with explosion-proof equipment. If it is ATEX approved, there will be an EX
name plate fixed on the unit.
Important:
You must use special non-sparking tools for all maintenance work on the
compressor.
Figure 1: EX name plate example
Important:
You must not use the compressor to complete the following actions:
• To evacuate the refrigeration plant of air and moisture.
• To put the refrigeration plant under air pressure in view of a pressure testing.
• As an air compressor.
Application of combustion engines
According to
EN 378/ISO 5149
, no other machinery should be installed in a refrigeration machine
room. Some refrigerant types may, to a certain extent, be absorbed by the fuel in a combustion
engine, and when the contaminated fuel reaches the fuel pumps, the refrigerant will “flash
out” (separate) and react on the increased temperature and pressure by creating acids, which will
destroy the pumps. However, check with the local authorities as exemptions to this rule may be
granted.
SAB 283-355 A-Frame OHU 6042 and OHU 7650 (including ATEX) Screw Compressor Unit