37
Energy Smart |
Horizontal Version
|
DIMENSIONS AND WEIGHT
Weight with packaging
Weight without packaging
ENY-SHP-170
35 kg
31 kg
INSTALLATION
The ENY-SHP-170 unit can easily be installed both horizontally and vertically.
Special support brackets are provided to install the unit horizontally on the ceiling and to install the unit vertically (especially in
gaps between plasterboard walls and load-bearing walls).
Vertical installation
Place the side ePM
1
55% - F7
downwards the unit.
The instruction manual indicates the appropriate maintenance clearance for each type of installation.
Horizontal installation
Spacer bars can be used to adjust the distance from the
ceiling. It is recommended to install the unit tilted towards
the side where the ePM
1
55% - F7 filter and the condensate
drain pipe are placed, in order to facilitate condensate drain-
age (provide a slope of 2% towards the filter and of 1% to-
wards the condensate drain pipe).
M5
F7
M5
F7
M5
F7
ENY-SHP-170 Pro Version
A
B
D
E
F
C
C
A
B
ØD
A
B
D
E
F
C
C
A
B
ØD
1125
1100
329
570
416
0 125
Содержание ENY-SP-180
Страница 2: ...Energy Smart...
Страница 4: ...Energy Smart 2...
Страница 17: ...15 Energy Smart...
Страница 25: ...23 Energy Smart Vertical Version ENY SP and ENY S Versions 12 5 4 3 2 1 11 10 9 8 7 6...
Страница 45: ...43 Energy Smart Horizontal Version Pro ENY SHP 150 Version 3 1 2 7 9 11 10 4 6 8 5...
Страница 47: ...45 Energy Smart Horizontal Version Pro ENY SHP 170 Version 1 2 3 5 4 3 7 10 9 11 5 6 8...
Страница 49: ...47 Energy Smart Horizontal Version Pro ENY SHP 270 Version 1 2 3 4 7 10 9 11 5 6 8...