DIGITAL TRANSDUCER
Configuration and CAN Interface
PRELIMINARY
CANopen
PCS III Technical Description CANopen 1r1 UK 310715.docx
09/02/2021
S2Tech srl
38
/
58
Index
Sub-
index
Name
Type Attri-
bute
Default-
value
Meaning
0x1010 0
Store parameter
UI8
ro
3
Number of Store options
1
Save all parameters UI32 rw
1
By writing the signature 'save' 0x73617665, all settings are saved on
the module.
2
Save
Communication
Parameters
UI32 rw
1
By writing the signature 'save' 0x73617665, the Communication
Parameters are saved on the module.
3
Save Application
Parameters
UI32 rw
1
By writing the signature 'save' 0x73617665, the Application Parameters
are saved on the module.
0x1011 0
Restore parameter
UI8
ro
2
Number of Store options
1
Restore all
parameters
UI32 rw
1
By writing the signature 'load' 0x64616F6C, all the factory default
settings are loaded.
2
Restore
Communication
Parameters
UI32 rw
1
By writing the signature 'load' 0x64616F6C, the factory default settings
of the communication area are loaded.
0x1012 0
COB-ID Time Stamp
Object
UI32 rw
100H
COB-ID of the Time Stamp Object
0x1014 0
COB-ID Emergency
message
UI32 rw
80H +
NodeID
COB-ID of the Emergency Object
0x1015 0
Emergency Inhibit
Time
UI16 rw
0
Emergency Object Inhibit time in multiples of 100uS
0x1016 0
Consumer Heartbeat
Time
UI16 rw
0
Cycle Time of the Heartbeat in multiples of 1mS
0x1017 0
Producer Heartbeat
Time
UI16 rw
0
Cycle Time of the Heartbeat in multiples of 1mS
0x1018 0
Identity Object
UI8
ro
4
Number of Entries
1
Vendor ID
UI32 ro
Vendor ID
2
Product Code
UI32 ro
Product Code
3
Revision Number
UI32 ro
Revision Number
4
Serial Number
UI32 ro
Serial Number