Connecting scheme
Parallel operation
Connecting scheme
Individual operation
SUPPLY VOLTAGE:
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 – 10 V devices on
AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage, the operating volt-
age input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!
When several devices are supplied by one 24 V AC voltage supply, it is
to be ensured that all ”positive“ operating voltage input terminals (+) of
the field devices are connected with each other and all ”negative“ opera-
ting voltage input terminals (–) (= reference potential) are connected
together (in-phase connection of field devices). All outputs of field de-
vices must be referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Circuitry
Circuitry
0...10V
0V/GND
0...10V
0V/GND
Power supply
AC 24V~
0V
DC 15-36V = GND
Circuitry
0...10V
0V/GND
V
Power supply
AC 24V~
0V
DC 15-36V = GND
G
Measuring transducers, calibrateable, with active output
Load resistance diagram
4 … 20 mA
Dependency of output voltage on output current
Output: ............................................. 4...20 mA
Connection: ..................................... 2-wire connection
Auxiliary energy: ............................ 15 ... 36 V DC ± 10 %,
supplied from 4...20 mA loop,
residual ripple, stabilised ± 0.3 V
Working resistance: ...................... Ra (Ohm) = (Ub-14 V) ⁄ 0.02 A
Output: ............................................. 0 - 10 V
Connection: ..................................... 3-wire connection
Auxiliary energy: ............................ 24 V AC ⁄ DC ± 20 %
Working resistance: ...................... minimum load resistance 5 kOhm
Accuracy: ......................................... ± 0,8 K
Measuring element: ....................... see table
Operating temperature: ............... transmitter - 30...+ 70 °C
Linearisation: .................................. temperature linear
according to DIN IEC 751
Linearity error: ............................... ± 0.3 % of measuring range
Standards: ....................................... CE conformity,
electromagnetic compatibility
according to EN 61326: 2006,
according to EMC directive
2004 ⁄ 108 ⁄ EC
TEMPERATURE RANGES:
When selecting measuring transducer ranges,
it is necessary to ensure that the maximum temperatures
permissible for sensor ⁄ enclosure are not exceeded !
Ambient temperature for measuring transducers:
- 30 ...+ 70 °C
Apparent ohmic resistance =
Voltage supply – internal current consumption (7.5 V)
20 mA
Ia
(mA)
12
10
8
6
4
2
0
0
1.5
0.5
2.5
3.5
4.5
1.0
2.0
3.0
4.0
Ua
(V)
800
700
600
500
400
300
250
50
200
10
15
20
25
30 35 36 40
Load resistance diagram
W
orking r
esis
tanc
e (Ohm)
Operating voltage (V DC)
Admissible
range
6
7
8