13
Connecting diagram
PREMASGARD
®
1110
Output:
with ⁄ without display
4 - 20 mA
Connecting diagram
PREMASGARD
®
1110
Output:
with ⁄ without display
0 -10 V
-
+
+
-
1 2 3
+UB 24
V DC
Output 4…20
mA GND
230V AC
PLC
Working
resistance
24V DC
-
+
+
-
1 2 3
230V AC
24V AC/DC
PLC
PC
+UB 24
V AC/DC
Output 0
-1
0
V
-UB AC/DC GND
Connecting scheme
Parallel operation
Connecting scheme
Individual operation
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 - 10 V devices on AC
supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (O V) of the input voltage!
When this device is operated on
DC supply voltage
, the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground
wire!
When several devices are supplied by one 24 V
AC voltage supply
, it is to
be ensured that all ”positive“ operating voltage input terminals (+) of the
field devices are connected with each other and all ”negative“ operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Circuitry
Circuitry
0...10V
0V/GND
0...10V
0V/GND
Power supply
AC 24V~
0V
DC 15-36V = GND
Circuitry
0...10V
0V/GND
V
Power supply
AC 24V~
0V
DC 15-36V = GND