G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element.
– In case of pollution, we recommend cleaning and recalibration in the factory. 
– The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.
– The relative humidity of 0 ...100 % is indicated by an output signal of 0 -10 V. The device operating range covers 10.0 ... 99.9 %  r. H.  

Beyond that range, mismeasurements or increased deviations may occur.

– When putting cover on, make sure sensors are not damaged. 
–  It is imperative to ensure the correct mounting position of this device to enable the necessary internal airflow. 
– Markings for mounting position (top, bottom) are found on the support ring. 
– If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV 

and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils 
of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve- 
ment of our products.

– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an 

EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Содержание HYGRASGARD RFF-UP

Страница 1: ...terputz im Fl chenschalterprogramm mit aktivem Ausgang G Operating Instructions Mounting Installation Room humidity and temperature sensors in wall panel switch programme with active output F Notice d...

Страница 2: ...HYGRASGARD RFF UP HYGRASGARD RFTF UP D G F r Ma zeichnung RFF UP Dimensional drawing RFTF UP Plan cot Einbauschema RFF UP Installation scheme RFTF UP Sch ma de montage...

Страница 3: ...lage auch gr er Ausgang Temperatur 0 10 V Umgebungstemperatur Lagerung 25 50 C Betrieb 5 50 C elektrischer Anschluss 3 oder 4 Draht siehe Anschlussbild 0 14 1 5 mm ber Steckklemmen Montage in UP Dose...

Страница 4: ...6 15 1 5 6 4 65 6 5 14 4 20 2 0 7 2 70 7 0 15 2 25 2 5 8 0 75 7 5 16 0 30 3 0 8 8 80 8 0 16 8 35 3 5 9 6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 Fortsetzung siehe rechts 100 10 0 2...

Страница 5: ...arstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen a...

Страница 6: ...sition and size Output temperature 0 10 V Ambient temperature storage 25 50 C operation 5 50 C Electrical connection 3 or 4 wire connection see connecting diagram 0 14 1 5 mm via plug terminals Instal...

Страница 7: ...6 15 1 5 6 4 65 6 5 14 4 20 2 0 7 2 70 7 0 15 2 25 2 5 8 0 75 7 5 16 0 30 3 0 8 8 80 8 0 16 8 35 3 5 9 6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 Continued at the right 100 10 0 20...

Страница 8: ...ogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products In case of any modifications made by the user all warranty...

Страница 9: ...e en fonction temp rature de l emplacement et de la position Sortie temp rature 0 10 V Temp rature ambiante stockage 25 50 C fonctionnement 5 50 C Raccordement lectrique 3 ou 4 fils voir sch ma de ra...

Страница 10: ...3 6 15 1 5 6 4 65 6 5 14 4 20 2 0 7 2 70 7 0 15 2 25 2 5 8 0 75 7 5 16 0 30 3 0 8 8 80 8 0 16 8 35 3 5 9 6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 Suite voir droite 100 10 0 20 0 T...

Страница 11: ...pplicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits E...

Страница 12: ...sch Jaeger Reflex Si RAL 9010 RFF UP U 0 10 GND 1 3 7 RFTF UP U 0 10 GND 1 3 7 r HYGRASGARD RFF UP RFTF UP Rev 2016 V10 RU 3 3 2 2 1 1 4 4 UB UB GND Output relative humidity 0 10V GND 3 3 2 2 1 1 4 4...

Страница 13: ...13 6 15 1 5 6 4 65 6 5 14 4 20 2 0 7 2 70 7 0 15 2 25 2 5 8 0 75 7 5 16 0 30 3 0 8 8 80 8 0 16 8 35 3 5 9 6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 100 10 0 20 0 0 50 C C UA IA A 0...

Страница 14: ...100 0 10 10 0 99 9 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V...

Страница 15: ...ations techniques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approv...

Страница 16: ...HYGRASGARD RFF UP HYGRASGARD RFTF UP D G F r...

Отзывы: