The humidity ⁄ temperature sensor
HYGR
ASGARD
®
RFF-UP ⁄ RFTF-UP
measures
the relative humidity and ⁄ or temperature of air. It converts the measurands humidity
and temperature into standard signals of 0 -10 V. Relative humidity (in % r. H.) is the
quotient of water vapour partial pressure divided by the saturation vapour pressure
at the respective gas temperature.
RFF-UP
⁄
RFTF-UP are applied in non-aggressive dust-free atmospheres in
refrigeration, air conditioning, ventilation and clean room technology, in residential
rooms, offices, hotels, technical rooms, meeting rooms and convention centres.
These measuring transducers are designed for exact detection of air temperature
and humidity. A digital long-term stable sensor is used as a measuring element for
humidity and temperature measurement.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC
Power consumption:
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Sensors:
digital humidity sensor
with integrated temperature sensor,
small hysteresis, high long-term stability
HUMIDITY:
Measuring range, humidity: 0...100 % r. H. (output corresponding to 0 -10 V)
Operating range, humidity:
10... 95 % r. H.
Deviation, humidity:
± 5 % r. H., at +20 °C
Output, humidity:
0 -10 V
TEMPERATURE:
Measuring range,
0...+50 °C
temperature:
(output corresponding to 0 -10 V)
Operating range,
temperature:
0...+50 °C
Deviation, temperature:
± 1 K, depending on installation location,
position and size
Output, temperature:
0 -10 V
Ambient temperature:
storage –25...+50 °C,
operation –5...+50 °C
Electrical connection:
3- or 4-wire connection (see connecting diagram),
0.14 - 1.5 mm² via plug terminals
Installation:
in in-wall flush box Ø 55 mm
Long-term stability:
± 1 % per year
Protection class:
III (according to EN 60 730)
Protection type:
IP 20 (according to EN 60 529)
Standards:
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC directive
2004 ⁄ 108 ⁄ EC
SWITCH PROGRAMME:
Manufacturer:
Busch-Jaeger Reflex Si
(other switch programs, manufacturers,
colours and prices upon request)
Enclosure:
plastic, standard colour alpine white
(similar RAL 9010) (other colours are possible on
request with colour variants depending on the
respective light switch programme)
G
HYGRASGARD
®
RFF - UP ⁄ RFTF - UP
Rev. 2016 - V10 GB
Connecting diagram
RFF - UP - U
In case of output 0 -10 V, GND connections (1)
and (3) are connected on the circuit board.
Connecting diagram
RFTF - UP - U
In case of output 0 -10 V, GND connections (1)
and (3) are connected on the circuit board.
3
3
2
2
1
1
4
4
UB +
UB -
GND
Output
relative
humidity
0-10V
GND
3
3
2
2
1
1
4
4
8
8
UB +
UB -
GND
Output
relative
humidity
0-10V
Output
temperature
0-10V
GND
HYGRASGARD
®
RFF - UP
– Room humidity sensors, in-wall
HYGRASGARD
®
RFTF - UP
– Room humidity and temperature sensors, in-wall
Type ⁄ WG01
Measuring Range ⁄ Readout
Humidity
Temperature
Output
Humidity Temperature
Item No.
RFF - UP - U
(active)
RF F -UP -U
0...100 % r. H.
–
0 -10 V
–
1201-5111-0008-180
RFTF - UP - U
(active)
RF T F -UP -U
0...100 % r. H.
0…+50 °C
0 -10 V
0 - 10 V
1201-5111-1000-017