S+S Regeltechnik HYGRASGARD KAVTF Series Скачать руководство пользователя страница 8

G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 

–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 

–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.

–  A suitable weather and sun protection hood must be used when installed outdoors.

–  In case of pollution, we recommend cleaning and recalibration in the factory.

–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.

–  The relative humidity of 0...100 % is indicated by an output signal of 0 -10 V or 4...20 mA. 

The device operating range covers 10.0...95 % r. H. Outside of that range, mismeasurements or increased deviations may occur.

–  When several sensors (0  -10 V) are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage 

source may be short-circuited. 

–  The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 

Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:

–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!

–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.

–  Consequential damages caused by a fault in this device are excluded from warranty or liability.

–  These devices must be installed and commissioned by authorised specialists.

–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.

–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.

–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.

–  Modifications of these records are not permitted.

–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 

initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY VOLTAGE:

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output volt-
age is measured against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to be 

ensured that all ”positive“ operating voltage input terminals (+) of the field 
devices are connected with each other and all ”negative“ operating voltage 
input terminals (–) (= reference  potential) are connected together (in-phase 
connection of field devices). All outputs of field devices must be referenced 
to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Содержание HYGRASGARD KAVTF Series

Страница 1: ...ung und aktivem Ausgang G Operating Instructions Mounting Installation Outdoor humidity sensors 2 0 for mixture ratio relative absolute humidity dew point enthalpy switchable and temperature with mult...

Страница 2: ...terfilter Standard plastic sinter filter standard Filtre fritt en mati re synth tique standard SF M Metall Sinterfilter optional Metal sinter filter optional Filtre fritt en m tal en option SF M Metal...

Страница 3: ...ichsumschaltung mit 8 umschaltbaren Messbereichen siehe Tabelle 0 100 r H default Arbeitsbereich Feuchte 10 95 r H ohne Betauung Abweichung Feuchte typisch 2 0 20 80 r H bei 25 C sonst 3 0 Abweichung...

Страница 4: ...in r H Zur besseren Ablesbarkeit ist eine Hintergrund beleuchtung vorhanden ber DIP Schalter kann anstelle der Standard Anzeige die Anzeige einer alternativen Ausgangsgr e eingestellt werden absolute...

Страница 5: ...fikationsbereiches entfallen alle Garantieanspr che Als AGB gelten ausschlie lich unsere sowie die g ltigen Allgemeinen Lieferbedingungen f r Erzeugnisse und Leistungen der Elektro industrie ZVEI Bedi...

Страница 6: ...le measuring ranges see table 0 100 r H default Operating range humidity 10 95 r H without formation of dew Deviation humidity typically 2 0 20 80 r H at 25 C otherwise 3 0 Deviations of other outputs...

Страница 7: ...n r H For improved legibility backlighting is provided DIP switches can be used to display an alternative output variable instead of the standard display Absolute humidity in g m Dew point in C Mixtur...

Страница 8: ...ing conditions of the mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are pos...

Страница 9: ...n m tal 16 mm L 32 mm HUMIDIT Plage de mesure humidit commutation multi gamme avec 8 plages de mesure commutables voir tableau 0 100 h r default Plage de service humidit 10 95 h r sans condensation ca...

Страница 10: ...ure lisibilit Avec l interrupteur DIP il est possible de r gler l affichage d une dimension de sortie alternative au lieu de l affichage standard Humidit relative en g m Point de ros e en C Rapport de...

Страница 11: ...llation et la mise en service des appareils doit tre effectu e uniquement par du personnel qualifi Seules les donn es techniques et les conditions de raccordement indiqu es sur la notice d instruction...

Страница 12: ...B U 4 20 A I 4 0 50 C default 20 80 C 35 75 C 35 35 C 35 80 C KAVTF 0 2 K 25 C AAVTF 0 6 K 25 C 2 0 10 B U 4 20 I 35 85 C 30 70 C 4 U 3 I 0 14 1 5 30 RAL 9016 72 x 64 x 37 8 Tyr 1 72 x 64 x 43 3 Tyr 1...

Страница 13: ...H 0 80 A H 0 50 C TP 20 80 C TP 0 85 ENT 0 50 C default 20 80 C 35 75 C 35 35 C 4 20 A 4 20 A 1201 3162 6000 029 KAVTF I DISPLAY 8x 4 4 20 A 4 20 A 1201 3162 6200 029 KAVTF U 8x 4 0 10 0 10 1201 3161...

Страница 14: ...10 4 20 10 0 95 0 10 24 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15...

Страница 15: ...es are used under a wide range of different conditions and loads beyond our control their particular suitability must be verified by each customer and or end user themselves Existing property rights m...

Страница 16: ...0 400 300 250 50 200 10 15 20 25 30 35 36 40 B rdendiagramm B rde Ohm Betriebsspannung DC V zul ssiger Bereich 800 700 600 500 400 300 250 50 200 10 15 20 25 30 35 36 40 Load resistance diagram Workin...

Отзывы: