19
F
AERASGARD
®
RCO
2
- W ⁄ RLQ - CO
2
- W ⁄ RFTM - LQ - CO
2
- W ⁄ RTM - CO
2
- SD
Rev. 2019 - V29
Schéma de raccordement
RFTM - LQ
- CO
2
- W
Interrupteur DIP (Baldur 2)
RFTM - LQ
- CO
2
- W
Sensibilité COV
DIP 1 DIP 2
LOW
OFF
OFF
MEDIUM (default)
O N
OFF
HIGH
OFF
O N
Type d’étalonnage COV
DIP 3
désactivé
OFF
activé (default)
O N
Teneur en CO
2
DIP 4
0...2000 ppm (default)
OFF
0...5000 ppm
O N
Type d’étalonnage CO
2
DIP 6
désactivé
OFF
activé (default)
O N
Affectation relais
DIP 7 DIP 8
CO
2
(default) :
600...1900 ppm / 900...4700 ppm
OFF
OFF
COV :
10...95 %
O N
OFF
Température :
+5...+48 °C
OFF
O N
Humidité :
10...95% h.r.
O N
O N
Sortie
DIP 9
Tension 0 -10 V (default)
OFF
Courant 4...20 mA
O N
Attention :
DIP 5
n'est pas affecté !
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO² CO²
VOC
VOC
r.H.
°C
12
11
13
1 2 3 4 5 6 7 8 9
ON
DIP
ON
ON
VOC
CO² Mode
NC
= Normally Closed
COM
= Common
NO
= Normally Open
Plug for
display
humidity in % r.H.
air quality (VOC)
Outputs
temperature in °C
–UB GND
+UB 2
4V A
C/DC
Output CO
²
in ppm
VOC
sensor
Reset
button
NC
COM
NO
relay
switch
point
Schéma de raccordement
RTM - CO
2
- SD
4
5
6
1 2 3
ZERO
CO²
free
free
Outputs
temperature in °C
–UB GND
+UB 2
4V A
C/DC
Output CO
²
in ppm
Reset
button