background image

G  

AERASGARD

®

  ACO

2

The maintenance-free microprocessor-controlled AERASGARD

®

 ACO

2

 is used to 

detect the CO

2

  content in air. This sensor is optionally available with or without 

display. The measurement signals are converted into standard signals of 0 -10 V. 
Optionally, this CO

2

 measuring trans ducer can be supplied with switching output. 

The CO

2

 content of air is determined by a dual beam NDIR sensor (non-dispersive 

infrared technology). The detection range of this CO

2

 sensor is calibrated for 

 standard  applications such as monitoring of residential rooms or conference 
rooms. Room ventil ation on an as - needed basis, improvement of well-being and 
customer benefit, increased comfort as well as a reduction of operating costs  
by energy conservation are only some of the beneficial results of employing 
 AERASGARD

®

 ACO

2

 sensors. 

A measuring system based on NDIR technology for CO

2

  measurement consists  

of a light source and a receptor. A certain range of wavelengths of light radiated 
off by the source is damped respectively absorbed by CO

2

 molecules in the 

 measured section. That damping is detected by the receptor. 

TECHNICAL DATA:

Power supply: ........................ 24 V AC ⁄ DC
Average power consumption: ....... < 3 VA  at 24 V DC
Sensor:................................. optical, dual beam sensor  (NDIR),  

with automatic self-calibration,

  

non-dispersive infrared technology, 
dual beam measuring method, 
including atmospheric pressure compensation

Measuring range: ....................

multi-range switching 

  

(selectable via DIP switches)  

0 … 2000 ppm;    0 … 5000 ppm;    0 … 10000 ppm

 

Output: ................................. 0 -10 V  or   

with potential-free changeover contact (24 V)

Measuring accuracy CO

2

: ......... ± 70 ppm plus 5 % of measured value

Pressure dependence: ............. <  ±  0,5 %  of  measured  value  ⁄  kPa  at   

compensated versions (standard),  
otherwise  ±  1,6  %  of  measured  value  ⁄  kPa    
(referred to standard pressure)

Temperature dependence:......... < 5 ppm  ⁄ K (referred to 20 °C)
Long-term stability:................. ± 1 % of final value per year
Gas exchange: ........................ by diffusion
Warm-up time:  ........................ ca. 1 hour
Ambient temperature: ............. 0 …+50 °C
Response time:  ....................... ca. 1 minute
Electrical connection: .............. 0.14 - 1.5 mm

2

,  

via screw terminals on circuit board

Enclosure: ............................. plastic, polyamide, 30 % glass-globe-reinforced,  

with quick-locking screws,  
colour pure white (similar RAL 9010)

Dimensions: ........................... 108  x  70  x  73.5 mm    (Thor  II)
Cable gland: ........................... M 16 x 1.5 ;  including  strain  relief
Protective tube: ..................... metal, Ø 20 mm,  

nominal  length  NL = 40 mm

Protection class:  .................... III  (according to EN 60 730)
Protection type:  ..................... IP 65  (according to EN 60 529)
Standards:  ............................ CE-conformity,   

electromagnetic compatibility  
according  to  EN  61 326 + A1 + A2,   
EMC directive 2004 ⁄ 108 ⁄ EC 

Optional: ............................... 8 - digit  display,  cutout  36 x14  mm  (W x H), 

for displaying actual CO

2

 content

Connecting diagram

 

ACO

2

Connecting diagram

 

ACO

2

 - W

Schematic diagram

 ACO

2

  

ACO

2

 - W

1

2

3

5

6

7

(ACO

2

-W)

min. max.

2000 5000 10000 aut

o

1 2 34

ON 

ATM

Sensor plug

Set CO

2

Output CO

2

 c

ont

ent

  0-10V

UB+ 24V A

C/DC

UB- GND

Br

eak

er

Normall

y open 

CO

range 

Switching 

threshold adjustment 

Measuring range

selection CO

2

Button and LED 

for manual CO

2

 

setting 

Atmospheric

pressure sensor

1

2

3

5

6

7

UB- GND
UB+ supply voltage 24V AC/DC

Output 0-10V  CO

2

-content in ppm

Breaker

Normally 

open contact

changeover  

(24 V)

1

2

3

UB- GND
UB+ supply voltage 24V AC/DC

Output 0-10V  CO

2

-content in ppm

Содержание 1501-1110-1001-022

Страница 1: ...usgang G Operating Instructions Mounting Installation On wall CO2 sensors respectively measuring transducers self calibrating with multi range switching and active output or active switching output F...

Страница 2: ...AERASGARD ACO2 D G F r Ma zeichnung Dimensional drawing Plan cot ACO2 73 40 73 5 17 108 40 20 M16x1 5...

Страница 3: ...her Luftdruckkompensation Messbereich Mehrbereichsumschaltung ber DIP Schalter w hlbar 0 2000 ppm 0 5000 ppm 0 10000 ppm Ausgang 0 10 V oder mit potentialfreiem Wechsler 24 V Messgenauigkeit CO2 70 pp...

Страница 4: ...t werden Sonde 2 Nach dem Anschlie en des Ger tes ist ein Dauerbetrieb von mindestens 10 Minuten bei Frischluft CO2 Gehalt 300 400 ppm sicherzustellen Die manuelle Kalibrierung des Ausgangssignals auf...

Страница 5: ...stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk r...

Страница 6: ...pm 0 10000ppm Output 0 10 V or with potential free changeover contact 24 V Measuring accuracy CO2 70 ppm plus 5 of measured value Pressure dependence 0 5 of measured value kPa at compensated versions...

Страница 7: ...bration of carbon dioxide measurement Manual calibration can be started independently from the position of the DIP4 switch by pushing the button probe 2 After connecting the device a period of at leas...

Страница 8: ...in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to hea...

Страница 9: ...e commutation multi gamme interrupteur DIP 0 2000 ppm 0 5000 ppm 0 10000 ppm Sortie 0 10 V ou avec inverseur libre de potentiel 24 V Incertitude de mesure 70 ppm 5 de la Vf D pendance de la pression 0...

Страница 10: ...nage manuel de la mesure du dioxyde de carbone L talonnage manuel peut tre lanc ind pendamment de la position de l interrupteur DIP4 en actionnant le bouton poussoir capteur 2 Apr s le branchement de...

Страница 11: ...nt pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie...

Страница 12: ...14 x ACO2 ACO2 W ACO2 ACO2 W 1 2 3 5 6 7 ACO2 W min max 2000 5000 10000 auto 1 2 34 ON ATM Sensor plug Set CO 2 Output CO 2 content 0 10V UB 24V AC DC UB GND Breaker Normally open CO2 range Switching...

Страница 13: ...2 DIP 3 0 2000 pp ON OFF OFF 0 5000 pp OFF ON OFF 0 10000 pp OFF OFF ON CO2 DIP 4 ON OFF 1 CO2 CO2 ACO2 ACO2 0 2000 5000 10000 pp 0 10 ATM 1501 1110 1001 022 ACO2_DISPLAY 0 2000 5000 10000 pp 0 10 AT...

Страница 14: ...50 C 7 300 400 ppm 10 7 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15...

Страница 15: ...niques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S R...

Страница 16: ...AERASGARD ACO2 D G F r...

Отзывы: