General notes

This device can be mounted in any position. The voltage output is short-circuit proof. Applying overvoltage at the voltage output will destroy this device. 
Pressure ranges are indicated on the device label. Applying measuring pressures beyond that range will cause mismeasurements and increased 
deviations or may destroy the device.

–  Attention! When leading in cables, make sure, they do not go under the board.  

This might buckle or damage hose connections! 

–  Pressure inputs are “poled“ i.e. the above-atmospheric pressure line must be connected at input P+  

and the below-atmospheric pressure line must be connected at input P–. 

–  At an adjusting element, the output signal can be offset by ±  10 % of the final value of the measuring range.  

In this way, possible ageing or drift effects can be compensated. 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 
and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:

–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!

–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.

–  Consequential damages caused by a fault in this device are excluded from warranty or liability.

–  These devices must be installed by authorised specialists only.

–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively 

valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.

–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.

–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.

–  Modifications of these records are not permitted.

–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Содержание 1301-1161-2160-200

Страница 1: ...halter W chter incl Anschluss Set G Operating Instructions Mounting Installation Volume flow measuring transducers switches monitors including connection set F Notice d instruction Convertisseur commu...

Страница 2: ...ARD 116x PREMASREG 116x D G F r Ma zeichnung PREMASGARD 116x Dimensional drawing PREMASREG 116x Plan cot PREMASGARD 116x PREMASREG 116x Anschl sse Connections Raccordements M16x1 5 48 37 4 13 9 73 5 7...

Страница 3: ...s Metall Druckart Differenzdruck Medium Luft und nicht aggressive nicht brennbare Gase Genauigkeit Typ 1161 1000 Pa 5 Pa Typ 1165 5000 Pa 25 Pa verglichen zu kalibriertem Referenzger t Summe von Linia...

Страница 4: ...001 0 277 x 10 3 0 0166 1 PREMASGARD 116x Volumenstrommessumformer schalter Premium PREMASREG 116x Volumenstrommessumformer w chter Premium Messbereich Druck Volumenstrom Typ WG01 Ausgang Display Art...

Страница 5: ...spannung gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be triebsspannungseingang UB f r 15 36 V DC Einspeisung und UB bzw GND...

Страница 6: ...1 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero UB 24V AC DC Ausgang Volumenstrom 0 10V in Pa GND GND UB GND S Stecker f r Display Offset Korrektur siehe Gra...

Страница 7: ...select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Stecker f r Display Offset Korrektur siehe Grafik ca 10 DIP Schalter Stecker Display Taster Nullpunkt setzen Kontakt seite 1 Zeil...

Страница 8: ...gangsspannung bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P Manuelles Einstellen des Offsets Voraussetzung DIP Schalter 6 ist auf ON Scha...

Страница 9: ...henden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhaltung der Bau und Sicherungsbestimmung zu gew hrleisten und G...

Страница 10: ...d other non aggressive non combustible gases Accuracy Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compared to the calibrated reference device Sum linearity hysteresis 1 of pressure range end value...

Страница 11: ...116x Volume flow measuring transducers switches Premium PREMASREG 116x Volume flow measuring transducers monitors Premium Measuring Range Pressure Volume Flow Type WG01 Output Display Item No 0 1000...

Страница 12: ...and UB or GND for ground wire When several devices are supplied by one 24 V AC voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected...

Страница 13: ...ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in P...

Страница 14: ...Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side 1st line showing actual pressure up to the measuring range limit Pa Pasc...

Страница 15: ...calibration the output voltage is 5 V at 0 Pa pressure difference with the offset knob in central position Output voltage 0 10 V for pressure difference P P Manual offset adjustment Precondition DIP s...

Страница 16: ...ded purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The purchaser has to adhere to the buildin...

Страница 17: ...tal Type de pression pression diff rentielle Milieu air et gaz non agressifs non inflammables Pr cision Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compar l appareil de r f rence talonn Somme de li...

Страница 18: ...PREMASGARD 116x Convertisseur commutateur de d bit Premium PREMASREG 116x Convertisseur contr leur de d bit Premium Plage de mesure pression d bit volumique Type WG01 sortie cran r f rence 0 1000 Pa P...

Страница 19: ...en 15 36 V cc et UB ou GND comme c ble de masse Si plusieurs appareils sont aliment s en 24V ca il faut veiller ce que toutes les entr es de tension positives des appareils de terrain soient reli es...

Страница 20: ...ax Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in Pa GND GND UB...

Страница 21: ...point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side La premi re ligne affiche la pression r elle jusqu la limite de la plage de mesure Pa pas...

Страница 22: ...e bouton offset est en position m diane est de 5V pour une diff rence de pression de 0 Pa Tension de sortie 0 10V pour diff rence de pression P P R glage manuel du point z ro Condition pr alable l int...

Страница 23: ...t tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en...

Страница 24: ...PREMASREG 116x 24 20 RL 5 1 24 2 2 24 1000 5000 0 10 B 20 50 C 4 6 x 11 4 6 1161 1000 5 1165 5000 25 1 0 1 C 0 7 200 1 10 30 RAL 9016 108 x 70 x 73 5 Thor 2 0 14 1 5 M 16 1 5 95 III EN 60 730 IP 65 IE...

Страница 25: ...0 001 0 06 0 0166 1 60 1 0 277 x 10 6 16 66 x 10 6 0 001 0 277 x 10 3 0 0166 1 PREMASGARD 1161 Premium PREMASREG 1160 Premium WG01 0 1000 PREMASGARD REG 1161 k 3000 94 800 PREMASGARD 1161 U DISPLAY 0...

Страница 26: ...0 10V UB AC DC GND GND r PREMASGARD 116x PREMASREG 116x Rev 2018 V13 RU PREMASGARD 116x PREMASREG 116x 6000m3 h C 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply A...

Страница 27: ...0 10V in Pa GND GND UB GND Contact pin side 1 12 11 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offse...

Страница 28: ...auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display...

Страница 29: ...29 PREMASGARD 116x PREMASREG 116x 0 xx 4 0 0 10 0 PREMASGARD 116x PREMASREG 116x xx xx 5 0 0 10 DIP 6 ON ON OFF auto offset OFFSET P 10...

Страница 30: ...30 r P P 10 ZVEI VDE EMV...

Страница 31: ...d sun protection optional Protection contre les intemp ries et le soleil en option Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestatte...

Страница 32: ...uss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement Ma zeichnung ASD 07 Dimensional drawing Pla...

Отзывы: