PREMASGARD

® 

116x / PREMASREG

® 

116x

1

st

 line showing volume flow rate value 

2

nd

 line showing corresponding measurement unit

At the PREMASREG

® 

116x in addition, the  switching  

status of the relay is indicated in the second line :

  Circle empty  =  relay in idle state 

  Circle solid  =  relay activated

    

At putting in operation, DIP switch 5 enables switching 
over to displaying pressure values.

 
 

1.  The device must be operative for at least 60 minutes before zero 

point setting is started. 

2.  Connect pressure connections P (+) and P (–) with a hose 

(differential pressure between the connections = 0 Pa). 

3.  Requirement: DIP-switch 6 is set to OFF. 

4.  To set the zero point, press pushbutton for 10 seconds without 

interruption. 

By pressing the button, a countdown of ca. 10 seconds is started. 
The yellow LED is flashing and the countdown counter is shown on the 
display (optional). 

After the countdown period has elapsed, zero point calibration takes 
place. This is indicated by continuous light of the LED, and on the 
display (optional) by switching from "AUTO 0" to "PROG 0". 

Note: When releasing the pushbutton during countdown (counter > 0), 
zero point setting is immediately aborted !

Automatic offset correction:

1 2 3 4

LED

auto

zero

up down

select

1 2 3 4 5 6

ON

DIP

min. max.

Offset

Offset

auto

zero

GND

GND

Pa

V+

Pushbutton

Zero point settin

Plug for display

Offset correction

see graph

ca. ± 10%

DIP switches 

Plug for 

display

Contact 

pin side

1

st

 line showing actual pressure up to the measuring range limit. 

Pa =  Pascal

 

    

Precondition: DIP switch 5 is set to ON.  

select

 

Pressing for more than 5 seconds =>  
switches to setup mode

 

A short push following thereafter =>  
switches to the next input value  
respectively terminates setup mode

up 

 

(arrow pointing up) increases the input value. Keeping it 
depressed increases the increment step by step by 
which the parameter is increased.

down 

▼ 

(arrow pointing down) decreases the input value. 
Pressing for longer increases the increment step by 
step by which the parameter is decreased.

Volume flow rate indication on the display:

Pressure reading at the display:

Setup button assignment:

Input k-value:   1…3000
1

st

 line showing set value 

2

nd

 line showing type, flashing at a one-second cycle

Input measurement unit: 
(Displayed unit of volume flow rate) 
0 = m

3

 ⁄ s,  1 = m

3

 ⁄ min,  2 = m

3

 ⁄ h,  3 = liters ⁄ s,  4=liters ⁄ min,  5 = liters ⁄ h

Input volume flow rate at max. output signal 10 V: 
Setting (measuring range end value  ^= 10 V) 

10% to 100% of max. possible volume flow rate 
in the selected measurement unit.

Input relay switching threshold at volume flow rate: 
Setting (relay switchpoint)  
10% to 100% of max. possible volume flow rate 
in the selected measurement unit.

Setup mode

Calculation formula – k-factor:

k = q ⁄ 

√(Pi) 

q = volume flow rate in m

3

 ⁄ h  

(Pi) = differential pressure in Pa

 

Adjustment range:  1…3000 

Содержание 1301-1161-2160-200

Страница 1: ...halter W chter incl Anschluss Set G Operating Instructions Mounting Installation Volume flow measuring transducers switches monitors including connection set F Notice d instruction Convertisseur commu...

Страница 2: ...ARD 116x PREMASREG 116x D G F r Ma zeichnung PREMASGARD 116x Dimensional drawing PREMASREG 116x Plan cot PREMASGARD 116x PREMASREG 116x Anschl sse Connections Raccordements M16x1 5 48 37 4 13 9 73 5 7...

Страница 3: ...s Metall Druckart Differenzdruck Medium Luft und nicht aggressive nicht brennbare Gase Genauigkeit Typ 1161 1000 Pa 5 Pa Typ 1165 5000 Pa 25 Pa verglichen zu kalibriertem Referenzger t Summe von Linia...

Страница 4: ...001 0 277 x 10 3 0 0166 1 PREMASGARD 116x Volumenstrommessumformer schalter Premium PREMASREG 116x Volumenstrommessumformer w chter Premium Messbereich Druck Volumenstrom Typ WG01 Ausgang Display Art...

Страница 5: ...spannung gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be triebsspannungseingang UB f r 15 36 V DC Einspeisung und UB bzw GND...

Страница 6: ...1 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero UB 24V AC DC Ausgang Volumenstrom 0 10V in Pa GND GND UB GND S Stecker f r Display Offset Korrektur siehe Gra...

Страница 7: ...select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Stecker f r Display Offset Korrektur siehe Grafik ca 10 DIP Schalter Stecker Display Taster Nullpunkt setzen Kontakt seite 1 Zeil...

Страница 8: ...gangsspannung bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P Manuelles Einstellen des Offsets Voraussetzung DIP Schalter 6 ist auf ON Scha...

Страница 9: ...henden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhaltung der Bau und Sicherungsbestimmung zu gew hrleisten und G...

Страница 10: ...d other non aggressive non combustible gases Accuracy Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compared to the calibrated reference device Sum linearity hysteresis 1 of pressure range end value...

Страница 11: ...116x Volume flow measuring transducers switches Premium PREMASREG 116x Volume flow measuring transducers monitors Premium Measuring Range Pressure Volume Flow Type WG01 Output Display Item No 0 1000...

Страница 12: ...and UB or GND for ground wire When several devices are supplied by one 24 V AC voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected...

Страница 13: ...ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in P...

Страница 14: ...Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side 1st line showing actual pressure up to the measuring range limit Pa Pasc...

Страница 15: ...calibration the output voltage is 5 V at 0 Pa pressure difference with the offset knob in central position Output voltage 0 10 V for pressure difference P P Manual offset adjustment Precondition DIP s...

Страница 16: ...ded purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The purchaser has to adhere to the buildin...

Страница 17: ...tal Type de pression pression diff rentielle Milieu air et gaz non agressifs non inflammables Pr cision Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compar l appareil de r f rence talonn Somme de li...

Страница 18: ...PREMASGARD 116x Convertisseur commutateur de d bit Premium PREMASREG 116x Convertisseur contr leur de d bit Premium Plage de mesure pression d bit volumique Type WG01 sortie cran r f rence 0 1000 Pa P...

Страница 19: ...en 15 36 V cc et UB ou GND comme c ble de masse Si plusieurs appareils sont aliment s en 24V ca il faut veiller ce que toutes les entr es de tension positives des appareils de terrain soient reli es...

Страница 20: ...ax Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in Pa GND GND UB...

Страница 21: ...point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side La premi re ligne affiche la pression r elle jusqu la limite de la plage de mesure Pa pas...

Страница 22: ...e bouton offset est en position m diane est de 5V pour une diff rence de pression de 0 Pa Tension de sortie 0 10V pour diff rence de pression P P R glage manuel du point z ro Condition pr alable l int...

Страница 23: ...t tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en...

Страница 24: ...PREMASREG 116x 24 20 RL 5 1 24 2 2 24 1000 5000 0 10 B 20 50 C 4 6 x 11 4 6 1161 1000 5 1165 5000 25 1 0 1 C 0 7 200 1 10 30 RAL 9016 108 x 70 x 73 5 Thor 2 0 14 1 5 M 16 1 5 95 III EN 60 730 IP 65 IE...

Страница 25: ...0 001 0 06 0 0166 1 60 1 0 277 x 10 6 16 66 x 10 6 0 001 0 277 x 10 3 0 0166 1 PREMASGARD 1161 Premium PREMASREG 1160 Premium WG01 0 1000 PREMASGARD REG 1161 k 3000 94 800 PREMASGARD 1161 U DISPLAY 0...

Страница 26: ...0 10V UB AC DC GND GND r PREMASGARD 116x PREMASREG 116x Rev 2018 V13 RU PREMASGARD 116x PREMASREG 116x 6000m3 h C 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply A...

Страница 27: ...0 10V in Pa GND GND UB GND Contact pin side 1 12 11 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offse...

Страница 28: ...auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display...

Страница 29: ...29 PREMASGARD 116x PREMASREG 116x 0 xx 4 0 0 10 0 PREMASGARD 116x PREMASREG 116x xx xx 5 0 0 10 DIP 6 ON ON OFF auto offset OFFSET P 10...

Страница 30: ...30 r P P 10 ZVEI VDE EMV...

Страница 31: ...d sun protection optional Protection contre les intemp ries et le soleil en option Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestatte...

Страница 32: ...uss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement Ma zeichnung ASD 07 Dimensional drawing Pla...

Отзывы: