S+S Regeltechnik 1301-1161-2160-200 Скачать руководство пользователя страница 12

12

Connecting diagram 

PREM

ASGARD

® 

116x - U 

Output: 

 

PREM

ASREG

® 

116x - U ⁄  W 

0 -10 V

  

with Display

-

+

+

-

1 2 3 4

230V AC

24V AC/DC

PLC

PC

+UB 24V A

C/DC

Output  0–10V

-UB  AC/DC

GND GND

PREMASGARD

®

 116x    PREMASREG

®

 116x 

Rev.  2018 - V13  GB

Mounting diagram 

PREM

ASGARD

® 

116x 

PREM

ASREG

® 

116x

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

6000m

3

/h

(C)

TYPES OF MONITORING:
(C) Ventilator: 

 

P1 (

+

) connected downstream of ventilator 

P2 (

) connected upstream of ventilator

Pressure connections at the pressure switch are marked with  
P1 (

+

) for higher pressure and P2 (

) for lower pressure.

Содержание 1301-1161-2160-200

Страница 1: ...halter W chter incl Anschluss Set G Operating Instructions Mounting Installation Volume flow measuring transducers switches monitors including connection set F Notice d instruction Convertisseur commu...

Страница 2: ...ARD 116x PREMASREG 116x D G F r Ma zeichnung PREMASGARD 116x Dimensional drawing PREMASREG 116x Plan cot PREMASGARD 116x PREMASREG 116x Anschl sse Connections Raccordements M16x1 5 48 37 4 13 9 73 5 7...

Страница 3: ...s Metall Druckart Differenzdruck Medium Luft und nicht aggressive nicht brennbare Gase Genauigkeit Typ 1161 1000 Pa 5 Pa Typ 1165 5000 Pa 25 Pa verglichen zu kalibriertem Referenzger t Summe von Linia...

Страница 4: ...001 0 277 x 10 3 0 0166 1 PREMASGARD 116x Volumenstrommessumformer schalter Premium PREMASREG 116x Volumenstrommessumformer w chter Premium Messbereich Druck Volumenstrom Typ WG01 Ausgang Display Art...

Страница 5: ...spannung gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be triebsspannungseingang UB f r 15 36 V DC Einspeisung und UB bzw GND...

Страница 6: ...1 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero UB 24V AC DC Ausgang Volumenstrom 0 10V in Pa GND GND UB GND S Stecker f r Display Offset Korrektur siehe Gra...

Страница 7: ...select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Stecker f r Display Offset Korrektur siehe Grafik ca 10 DIP Schalter Stecker Display Taster Nullpunkt setzen Kontakt seite 1 Zeil...

Страница 8: ...gangsspannung bei Mittelstellung des Offsetreglers 5V bei OPa Druckdifferenz Ausgangsspannung 0 10V f r Druckdifferenz P P Manuelles Einstellen des Offsets Voraussetzung DIP Schalter 6 ist auf ON Scha...

Страница 9: ...henden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhaltung der Bau und Sicherungsbestimmung zu gew hrleisten und G...

Страница 10: ...d other non aggressive non combustible gases Accuracy Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compared to the calibrated reference device Sum linearity hysteresis 1 of pressure range end value...

Страница 11: ...116x Volume flow measuring transducers switches Premium PREMASREG 116x Volume flow measuring transducers monitors Premium Measuring Range Pressure Volume Flow Type WG01 Output Display Item No 0 1000...

Страница 12: ...and UB or GND for ground wire When several devices are supplied by one 24 V AC voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected...

Страница 13: ...ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in P...

Страница 14: ...Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side 1st line showing actual pressure up to the measuring range limit Pa Pasc...

Страница 15: ...calibration the output voltage is 5 V at 0 Pa pressure difference with the offset knob in central position Output voltage 0 10 V for pressure difference P P Manual offset adjustment Precondition DIP s...

Страница 16: ...ded purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be observed The purchaser has to adhere to the buildin...

Страница 17: ...tal Type de pression pression diff rentielle Milieu air et gaz non agressifs non inflammables Pr cision Type 1161 1000 Pa 5 Pa Type 1165 5000 Pa 25 Pa compar l appareil de r f rence talonn Somme de li...

Страница 18: ...PREMASGARD 116x Convertisseur commutateur de d bit Premium PREMASREG 116x Convertisseur contr leur de d bit Premium Plage de mesure pression d bit volumique Type WG01 sortie cran r f rence 0 1000 Pa P...

Страница 19: ...en 15 36 V cc et UB ou GND comme c ble de masse Si plusieurs appareils sont aliment s en 24V ca il faut veiller ce que toutes les entr es de tension positives des appareils de terrain soient reli es...

Страница 20: ...ax Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offset correction see graph ca 10 DIP switches Plug display UB 24V AC DC Output volume flow rate 0 10V in Pa GND GND UB...

Страница 21: ...point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display Contact pin side La premi re ligne affiche la pression r elle jusqu la limite de la plage de mesure Pa pas...

Страница 22: ...e bouton offset est en position m diane est de 5V pour une diff rence de pression de 0 Pa Tension de sortie 0 10V pour diff rence de pression P P R glage manuel du point z ro Condition pr alable l int...

Страница 23: ...t tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en...

Страница 24: ...PREMASREG 116x 24 20 RL 5 1 24 2 2 24 1000 5000 0 10 B 20 50 C 4 6 x 11 4 6 1161 1000 5 1165 5000 25 1 0 1 C 0 7 200 1 10 30 RAL 9016 108 x 70 x 73 5 Thor 2 0 14 1 5 M 16 1 5 95 III EN 60 730 IP 65 IE...

Страница 25: ...0 001 0 06 0 0166 1 60 1 0 277 x 10 6 16 66 x 10 6 0 001 0 277 x 10 3 0 0166 1 PREMASGARD 1161 Premium PREMASREG 1160 Premium WG01 0 1000 PREMASGARD REG 1161 k 3000 94 800 PREMASGARD 1161 U DISPLAY 0...

Страница 26: ...0 10V UB AC DC GND GND r PREMASGARD 116x PREMASREG 116x Rev 2018 V13 RU PREMASGARD 116x PREMASREG 116x 6000m3 h C 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply A...

Страница 27: ...0 10V in Pa GND GND UB GND Contact pin side 1 12 11 13 2 3 4 LED auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero Pushbutton Zero point setting NC NO Plug for display Offse...

Страница 28: ...auto zero up down select 1 2 3 4 5 6 ON DIP min max Offset Offset auto zero GND GND Pa V Pushbutton Zero point settin Plug for display Offset correction see graph ca 10 DIP switches Plug for display...

Страница 29: ...29 PREMASGARD 116x PREMASREG 116x 0 xx 4 0 0 10 0 PREMASGARD 116x PREMASREG 116x xx xx 5 0 0 10 DIP 6 ON ON OFF auto offset OFFSET P 10...

Страница 30: ...30 r P P 10 ZVEI VDE EMV...

Страница 31: ...d sun protection optional Protection contre les intemp ries et le soleil en option Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestatte...

Страница 32: ...uss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccordement Ma zeichnung ASD 07 Dimensional drawing Pla...

Отзывы: