G  

Measuring transducers, calibrateable, with active output  

Load resistance diagram 

4...20 mA 

Dependency of output voltage on output current

Ia

 (mA)

12

10

8

6

4

2

0

0

1.5

0.5

2.5

3.5

4.5

1.0

2.0

3.0

4.0

Ua

  (V)

800

700

600

500

400

300
250

50

200

10

15

20

25

30 35 36 40

Load resistance diagram

W

orking r

esis

tanc

e  (Ohm)

Operating voltage  (V DC)

Admissible

  range

TEMPERATURE RANGES:

When selecting measuring transducer ranges,  
it is necessary to ensure that the maximum temperatures  
permissible for sensor  ⁄ enclosure are not exceeded !

Ambient temperature for measuring transducers:  
– 30 ...+ 70 °C

Apparent ohmic resistance  =  see load resistance diagram

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
 supply  voltage. 

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Содержание 1101-3121-0049-810

Страница 1: ...ture measuring transducer including mounting flange calibratable with multi range switching and active output F Notice d instruction Convertisseur de temp rature de gaz de fum e en gaine y compris bri...

Страница 2: ...ung RGTM1 Dimensional drawing Plan cot RGTM1 Messeinsatz Measuring insert Insert de mesure RGTM1 optional IP 65 RGTM1 standard IP 54 RGTM1 Anschlusskopf Connecting head T te de raccordement 80 73 M20...

Страница 3: ...Spanne Nullpunkt sind einstellbar TECHNISCHE DATEN Spannungsversorgung 24 V AC DC 10 bei U Variante 15 36 V DC bei I Variante b rdenabh ngig Restwelligkeit stabilisiert 0 3 V B rde max 750 Ohm 24 V DC...

Страница 4: ...al ist mit einem Messger t abzugreifen Hierbei wird die Ausgangsspannung gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be tri...

Страница 5: ...agen sind nicht gestattet Bei Reklamationen werden nur vollst ndige Ger te in Original ver packung angenommen Hinweise zur Montage Der Einbau hat unter Ber cksichtigung der einschl gigen f r den Mess...

Страница 6: ...ible range and zero point are adjustable TECHNICAL DATA Power supply 24 V AC DC 10 for U variant 15 36 V DC for I variant depending on working resistance residual ripple stabilised 0 3 V Working resis...

Страница 7: ...a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on AC supply voltage The output sign...

Страница 8: ...ns Modifications of these records are not permitted In case of a complaint only complete devices returned in original pack ing will be accepted Notes on installation Mounting shall take place while ob...

Страница 9: ...in d chelle et le point z ro sont r glables CARACT RISTIQUES TECHNIQUES Alimentation en tension 24 V ca cc 10 pour variante U 15 36 V cc pour variante I d pend de la charge ondulations r siduelles sta...

Страница 10: ...ment s en courant alternatif Le signal de sortie doit tre pr lev avec un appareil de mesure Ce faisant la tension de sortie est mesur e par rapport au potentiel z ro O V de la tension d entr e Si cet...

Страница 11: ...Il est interdit de modifier la pr sente documentation En cas de r clamation les appareils ne sont repris que dans leur embal lage d origine et que si tous les l ments de l appareil sont complets Cons...

Страница 12: ...U IP54 U RGTM1 U 200MM Pt1000 0 10 200 1101 3121 0049 810 RGTM1 U 250MM Pt1000 0 10 250 1101 3121 0059 810 RGTM1 U 300MM Pt1000 0 10 300 1101 3121 0069 810 RGTM1 U 400MM Pt1000 0 10 400 1101 3121 0089...

Страница 13: ...50 200 10 15 20 25 30 35 36 40 Load resistance diagram Working resistance Ohm Operating voltage V DC Admissible range 30 70 C c 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND...

Страница 14: ...22 24 26 28 30 2 TH ms xx TH VA xx TH VA xx 90 P 1 T 100 200 C P 20 bar T 100 C P 20 bar T 200 C P 1 T 100 200 C P 20 bar T 100 C P 20 bar T 200 C v c v c l l m 8 x 0 75 1 4571 TH VA xx TH VA xx 90 8...

Страница 15: ...d loads beyond our control their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our p...

Страница 16: ...t1000 1 2 3 4 5 ON DIP offset 1 2 3 SPS PC 230V AC 24V DC 24V 0 10V GND Pt1000 1 2 3 4 5 ON DIP offset 1 2 3 PLC PC 230V AC 24V DC max zul ssige Temperaturbereiche beachten observe max permissible tem...

Отзывы: