20.2 maintenance
Depending on the results of the inspection carry out any maintenance and if necessary any preventive maintenance.
Possible actions include:
at a) The remarks and comments of the client must be taken seriously and the cause(s) of any faults or problems
must be found.
at b) The pressure of the installation must be between 1 and 2 bar: any possible leaks in the system must be
identified; if necessary, have a pipework engineer solve the problem.
at c) Possible leaks or weeping must be resolved immediately.
at d) In case of water leakage or ingress from the air supply pipe, the cause must be found.
at e) If the condensation in the siphon is highly contaminated, the siphon must be rinsed. With the burners removed,
use a filling hose to insert water into the heat exchanger, which will automatically reach the siphon.
at f) Draw your conclusions from the service screen and attend to those parts that have caused any faults.
at g) and at h)
If necessary, adjust the gas setting on the gas valves.
at i) If the in built pumps make an un-natural noise, and in particular if the pumps are more than 5 years old, it is
recommended that the pumps should be replaced by way of preventive action.
Note the pumps are fully modulating and do have characteristic a “yet yet” noise which is normal at low speeds.
at j) NEVER CLEAN THE BURNER ITSELF
If the interior of the heat exchanger is contaminated and/or there is a deposit on the surfaces of the coiled
stainless steel pipes, the latter must be removed with a hard brush or citric acid. (DO NOT USE A STEEL
BRUSH!) Then remove any dirt with a vacuum cleaner
at k) If dirt has deposited on the fan blades, each blade must be carefully cleaned, until the blade material is visible
again. If this is not done evenly the fan will not rotate properly and be out of balance.
at I) Carefully bend the electrode without touching the burner, until the correct distance has been reached
IMPORTANT NOTE
IF ANY WATER CARRYING JOINT WITHIN THE BOILER IS DISASSEMBLED THEN THE “0” RING
SEAL MUST ALWAYS BE REPLACED, LIKEWISE IF ANY OTHER SEAL IS NOTED TO BE DEFORMED
THEN THEY SHOULD ALSO BE REPLACED.
WATER SEALING “0” RINGS ARE A ONE TIME USE ONLY AND SHOULD NOT BE RE-USED.
Cancelling the Service Message
Following the maintenance operations, the service message (when
displayed) must be cancelled. This is done by pressing and holding in the service button for at least 10 seconds.
Содержание MICROMAT EC 45
Страница 1: ......
Страница 2: ......
Страница 32: ...32 17 0 electrical connections E n e r g y T e c h n o l o g y Ltd plan of internal electrical connections ...
Страница 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Страница 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Страница 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Страница 56: ......