26
16.0 hydraulic system
design
E n e r g y T e c h n o l o g y
Ltd.
system type 4
Typical Single MICROMAT EC boiler installation serving heating & domestic hot water. Hot water is priority
and is served via a divertor valve and the boiler's in built circulating pump where index loss through HWS
primaries is less than 1 metre. Heating circuit index loss exceeds 1 metre and is served via a low velocity
mixing header and a separate pump. Heating flow temperature may be fixed/constant or weather variable.
PR01=Pump regulation module from RVR Ltd.
Allows heating pump to be driven from boiler,
providing for auto operation, frost protector
running & summer standstill exercising.
Must be used where RE2132 modulating room unit
is installed. Max pump motor load 2A.
Divertor valve will require SPDT relay if not spring
return.
Divertor valve must be so installed as to spring
return to heating.
OS = Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C = Room temperature controls e.g. RE2132
modulating room unit from RVR Ltd., or,
separated time clock & room thermostat.
S = HWS sensor from RVR Ltd. Gives 24hr HWS
operation.
W/T = Alternative to "S" where "W" is a time switch
in series with a cylinder thermostat "T". Allows
for timed HWS.
Flow to
system circuits
Return from
system circuits
IV
IV
Strainer
DOC
Low velocity mixing header
Max. velocity 0.5m/s
Safety Valve
AV
PRO 1
Micromat EC
boiler
C
AV's
Condensate
LSV
IV
Expansion Vessel
CWM
DOC
S
T
W
Calorifier
DOC
DOC
OS
Содержание MICROMAT EC 45
Страница 1: ......
Страница 2: ......
Страница 32: ...32 17 0 electrical connections E n e r g y T e c h n o l o g y Ltd plan of internal electrical connections ...
Страница 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Страница 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Страница 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Страница 56: ......