![RVP 6536 SERIES Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/rvp/6536-series/6536-series_service-manual_1503350027.webp)
27
Check 115 VAC To System #2
To Compressor #2 Relay And
Common #2
Restore 115 VAC
System #1 Compressor Operating
See Compressor #1
Checkout
12 VDC To W&B At Thermostat
12 VDC To Pin Connectors
W&B On P.C. Board. Also
T10 & T3B (See Figure 14).
Replace Thermostat If System #2
Should Be Calling And Is Not
According To Operation Manual.
NO
NO
O
K
NO
O
K
Check All Pin Terminals And
Connections From Thermostat.
Replace Lifeline If Necessary.
NO
O
K
O
K
Check Compressor #2
Relay Operation
Replace Relay If 12 VDC Is
Present And Relay Won’t
Close Or If Relay Is Welded
NO
O
K
Check Compressor Start Device.
Check For Proper Wiring To
Compressor #2. Check Compressor
Run Capacitor. Check Compressor
Motor Windings For Open Or Ground.
NO
Reconnect Wiring Or Replace
Components As Necessary
COMPRESSOR #2 CHECKOUT
THERMOSTAT CALLING STAGE 2
COOLING ONLY
Note: All Operating Functions Subject To Thermostat Time Delays
Содержание 6536 SERIES
Страница 1: ...SERVICE MANUAL FOR 6536 SERIES PACKAGED HEAT PUMPS...
Страница 4: ...4 4 UNIT SPECIFICATIONS AND IDENTIFICATION...
Страница 18: ...18 17 WIRING DIAGRAM 6536 Series Packaged Heat Pump 2 Compressor...
Страница 19: ...19 18 WIREBOX COMPONENT CHECKOUT...
Страница 28: ...28 CHECKOUT OUTDOOR BLOWER LOW SPEED HEATING AND COOLING MODES...
Страница 36: ...RV Products A Division of Airxcel Inc P O Box 4020 Wichita KS 67204 1976A281 1 00 PP...