Ruud PowerVent AP14236 Скачать руководство пользователя страница 22

Tee fitting for vertical hot 

water supply lines.

Hot water 

supply to  

house

From HOT  

outlet on  

water heater

Hot water  

supply to  

heating 

unit

Supplemental instructions for gas water heaters installed 

in potable water/space heating applications.

Local codes or plumbing authority requirements may vary from the instructions or diagrams provided 

in this manual and take precedent over these instructions.

Tee fitting for horizontal hot 

water supply lines.

From HOT  

outlet on  

water heater

Hot water 

supply to 

house

Hot water supply 

to heating unit

Combination Potable Water and Space Heating Application

Tee fitting must be installed as shown. 

This ensures that any air in the water lines 

will be purged through the domestic water 

faucets and showers.

DANGER: When this system 

requires water for space heating at 

elevated temperatures (above 125°F 

[52°C.]), a mixing or tempering valve 

must be installed in the hot water 

supply line to the house in order to 

reduce the scald hazard potential.

DANGER: Any piping or components 

used in the installation of this water 

heater in a combination potable and 

space heating application must be 

suitable for use with drinking water.

DANGER

:

 If this water heater is 

installed in an application intended to 

supply domestic hot water needs and 

hot water for space heating purposes, 

do not connect the heater to an existing 

heating unit or components of a heating 

system that have previously been used 

with a non drinking water system. Toxic 

chemicals such as those used for boiler 

treatment may be present and will 

contaminate the drinking water supply 

causing possible health risks. Never  

introduce toxic chemicals, such as those 

used for boiler treatment, into this 

system.

Notice:

  50' - 0" maximum distance from 

water heater to fan coil (developed length) 

is required for Massachusetts State.

Typical Piping Diagram for Combination Potable/Space Heating Installation

Spring loaded check valve in heating unit 
hot water supply line and cold water return 

line (not supplied with water heater)

NOTE: This check valve is incorporated 

in some heating units. Refer to the 

installation instructions supplied with 

specific heating unit to determine if it is 

required.

All water piping shall be insulated in 

accordance with Local and State Energy 

Code.

Isolation valve in 

cold water return line 

from heating unit (not 

supplied with water 

heater)

Nominal 3/4" size mixing or tempering valve 

(refer to warning above).  Follow mixing or 

tempering valve manufacturer’s instructions for 

installation of the valve.

Temperature and pressure relief 

valve discharge line

Air Handler

Drain valve
(not supplied with
 water heater)

Hot water  

to space heater

Temperature and Pressure Relief 

Valve, tie to location approved by 

local code

See diagrams above for proper  

pipe application for vertical  

or horizontal supply lines.

Isolation valve in hot water supply line 

to heating unit (not supplied with water 

heater)

3/4" cold water supply

3/4" Tempered 

domestic hot water 

supply to house.

Gas line to water heater

6” Air Gap

Combustion Air Inlet 

Openings

2 Gallon Thermal 

Expansion Tank (if 

required-not supplied 

with water heater)

Air vent

Heat Trap
6” Min.

3/4" Shut-Off Valve (Typ.)

3/4" Check Valve with 1/8" Hole

Pressure Gauge

3/4" Shut-Off Valve (Typ.)

3/4" Shut-

Off Valve 

(Typ.)

Hot water coil

All bronze pump.

Check valve 

internal in pump.

Air bleed valve.

Water Sample Tap.

 T

FAN

ON

OFF

HEAT

COOL

To HVAC Unit.

Electronically controlled pump timer.  

Activates every 6 hours for 60 seconds.  

Wire to bronze pump.

3/4" HWS & HWR 

to Heating Coil.

Minimum of 2'-0" developed length 

of 3/4" pipe.

Water Heater drain pan installed in 

accordance with the Local and State 

Code

Water Heater to be in accordance with 

the Local and State Energy Code

Gas Fired 

Water Heater 

Gas Direct Vent discharge 

must comply with Local 

and State Codes

Vacuum Relief Valve

(Not Supplied)

If required, install per local codes

and valve manufacturer’s

instructions.

 

120° to 130°  

         

140°  

22

Gas  Control (Thermostat)

Содержание PowerVent AP14236

Страница 1: ...he basic directions and recommendations for the proper installation and adjustment of the water heater and two for the owner operator to explain the features operation safety precautions maintenance a...

Страница 2: ...time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may not need to ca...

Страница 3: ...s paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water hea...

Страница 4: ...rature Dial D A N G E R HOT Water temperature over 125 F can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being scalded See instruction manual...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...installation For residential water heaters of a capacity greater than 52 gallons consult the local building jurisdiction for acceptable bracing procedures Have the installer show you the location of t...

Страница 7: ...ate a shut down condition of the water heater which will not allow the water heater to ignite until examined by a Qualified Service Technician The water heater must be located so it is not subject to...

Страница 8: ...than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure If horizontal ducts are used to communicate with the outdoors each opening must have a minimum net...

Страница 9: ...ondition and eliminating the repeated operation of the relief valve Other methods of controlling thermal expansion are also available Contact your installing contractor water supplier or plumbing insp...

Страница 10: ...ncealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed in the discharge line To Fill the Water Heater Make certain that the drain valve...

Страница 11: ...s supply piping at pressures equal to or less than 3 8 psi 10 5 w c for natural gas or 1 2 psi 14 w c for LP gas Gas Supply The branch gas supply line to the water heater should be clean 1 2 black ste...

Страница 12: ...nual have been met Carefully inspect the entire venting system for any signs of cracks or fractures particularly at the joints between elbows or other fittings and the straight length of vent pipe Che...

Страница 13: ...s For the 2 vent one 90 elbow is approximately equal to 6 feet of vent pipe One 45 elbow is approximately equal to 3 feet of vent pipe Minimum vent length for 2 vent pipe is one 1 foot of vertical pip...

Страница 14: ...t Pipe Length in Feet ft 0 Maximum Altitude See chart on upper left One 1 None 95 One 1 One 1 92 5 Two 2 None 90 Two 2 One 1 87 5 Three 3 None 85 Three 3 One 1 82 5 Four 4 None 80 Four 4 One 1 77 5 Fi...

Страница 15: ...xterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result in severe damage to th...

Страница 16: ...without additional support for vent Four 4 feet from any gable dormer or other roof structure with building interior access i e vent window etc Ten 10 feet from any forced air inlet to the building A...

Страница 17: ...the joint with a rag Allow 15 minutes before handling Cure time will vary according to fit temperature and humidity NOTICE Stir the solvent cement frequently while using Use a natural bristle brush or...

Страница 18: ...nce with latest edition of the National Electric Code ANSI NFPA No 70 Refer to the figures below for water heater internal wiring NOTE It is not recommended that this unit be installed on a GFCI circu...

Страница 19: ...ication of an external insulation blanket to this water heater pay careful attention to the following so as not to restrict the proper function and operation of the water heater Do not cover the opera...

Страница 20: ...cess Door unless absolutely necessary This should only be done by a qualified service technician A new burner access door gasket must be installed on any burner access door that has been removed DON T...

Страница 21: ...and free of leaks Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for possible gas l...

Страница 22: ...ating Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating units...

Страница 23: ...s phone Follow the gas suppliers Do not try to light any appliance Do not touch any electric switch do not use any phone in your building WHAT TO DO IF YOU SMELL GAS 9 10 Stop Read the safety informa...

Страница 24: ...temperature of the water in the water heater can be regulated by pressing the buttons on the front of the gas control thermostat Safety and energy conservation are factors to be considered when selec...

Страница 25: ...refore always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Also always supervise young children or others who are...

Страница 26: ...as valve which will extinguish the main burner flames The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to cle...

Страница 27: ...ef valve on the water heater discharges periodically this may be due to thermal expansion in a closed water system Contact the water supplier or your plumbing contractor on how to correct this DO NOT...

Страница 28: ...ealed area If the burner access door is removed the burner access door gasket must be replaced For cleaning remove the burner from the water heater A vacuum cleaner can be used on the burner and floor...

Страница 29: ...Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank The anode rod is slowly consumed thereby elimin...

Страница 30: ...inlet openings on water heater jacket Not enough combustion or Proper operation of the water heater requires air for ventilation air supplied to combustion and ventilation See the Combustion and the...

Страница 31: ...ion Shutoff System Contact a qualified service technician tripped Water is too hot The gas control thermostat See the Water Temperature Setting of The Water is set too high Heater section of this manu...

Страница 32: ...d A B C Error in the hot surface ignitor cir cuit 1 Check that all wiring is correct and secure 2 Replace hot surface ignitor A B C System in lockout 1 Gas supply is off or too low to operate 2 Hot su...

Страница 33: ...hermostat burners vent connectors or other safety devices Refer repairs to qualified service personnel Use only original equipment replacement parts Blower Assembly Flue baffle and hanger Anode rod He...

Страница 34: ...34 Notes...

Страница 35: ...35 Notes...

Страница 36: ...an attic the hard wired carbon monoxide detec tor with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be...

Отзывы: