8 MC500-1ERV

INSTALLATION CHECK LIST

MiniCore Model #           

Serial #      

Owner 

          

Owner Phone # 

      

Owner Address  

           

 

 

 

 

 

 

Installing Contractor 

        

Start Up Mechanic 

     

 

‰

Inspect the unit for transit damage and report any damage on the carrier's freight bill.

 

‰

Check model number to insure it matches the job requirements. 

 

‰

Install field accessories and unit adapter panels as required. Follow accessory and unit installation manuals. 

 

‰

Verify field wiring, including the wiring to any accessories. 

 

‰

Check all multi-tap transformers, to insure they are set to the proper incoming voltage.

 

‰

Verify blower wheels are centered. Realign if needed.

 

‰

Prior to energizing the unit, inspect all the electrical connections. 

 

‰

Power the unit. Bump the motor relay to check rotation. If blower motor fans are running backwards, de-

energize power to the unit, then swap reversing plug on motors to change direction. Re-check. 

 

‰

Perform all start up procedures outlined in the installation manual shipped with the unit.

 

‰

Fill in the Start Up Information as outlined on the opposite side of this sheet. 

 

‰

Provide owner with information packet. Explain the thermostat and unit operation. 

START UP INFORMATION SHEET

VOLTAGE - MCV UNIT

Incoming Voltage L1-L2  

 

 

Running Voltage L1-L2    
Secondary Voltage    

AMPERAGE - MCV MOTORS

Intake Motor: Nominal HP       Rated Amps  

 

   Running Amps    

Exhaust Motor: Nominal HP 

      Rated Amps  

 

   Running Amps    

Wheel Motor: Nominal HP 

     Rated Amps  

 

   Running Amps    

AIRFLOW

Intake Design CFM 

       Pressure Drop  

 

  Calculated CFM    

Exhaust Design CFM       Pressure Drop  

 

  Calculated CFM    

Amb. db Temp         

   Return Air db Temp*    

 

   Tempered Air db Temp*  

Amb. wb Temp 

      Return Air wb Temp*    

 

   Tempered Air wbTemp*  

* Measure after 15 minutes of run time 

Содержание MiniCORE MCV-500

Страница 1: ...nergy by transferring heat energy across two opposing air streams using a polymer core heat exchanger This process works in the summer by rejecting the heat energy from incoming intake air and in the winter by conserving the heat energy from the exhaust air allowing outdoor ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of the he...

Страница 2: ...re 3 High voltage 115V Connect the high voltage wires to L1 Hot L2 Common hook the ground wire to the provided grounding nut See Wiring Diagrams on Pages 6 7 208 230V Single phase Connect the high voltage wires to L1 Hot L2 Common connect the ground wire to the provided ground nut Check Voltage into the unit and adjust the voltage input to the transformer from 230V to 208V if necessary by switchin...

Страница 3: ...read across the MiniCore Figure 4 B Air Balancing Adjustment 1 Remove plastic plugs in access panels 4 total 2 With a manometer measure pressure drop inches of water column diagonally across the MiniCore Unit CFM for 3 speed PMC motors is determined then by referring to Table 1 on Page 5 3 Repeat the same process for the other airflow vector of MiniCore 4 System can be balanced by adding dampers t...

Страница 4: ...s together 2 Remove the center divider panel by removing the two 5 16 screws at with end of the panel on the side of the MiniCore 3 Carefully slide the core outwards B Filter Removal See Figure 6 1 Open the Filter Access panel by opening the two spring loaded latches to expose filters 2 Slide filters outwards Figure 5 Unit A B C MCV500 42 1 4 51 15 1 2 MCV1000 20 3 4 C B ...

Страница 5: ...Static Pressure in wc 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 CFM Input Voltage v 2 38 3 138 80 15 4 238 182 121 52 5 339 284 226 164 101 50 6 439 386 332 275 216 164 7 539 488 438 386 331 278 227 175 123 71 19 8 640 590 543 498 446 393 347 298 249 200 151 9 740 692 649 609 561 507 467 421 375 330 284 10 741 693 650 610 562 508 456 410 373 326 291 Performance Test for MCV1000 with ECM Motor Su...

Страница 6: ...6 MC500 1ERV MCV500 MCV1000 UNIT WIRING DIAGRAM Notes 1 Selective voltage terminal for proper unit voltage Mini Ventilator W Factory Installed Options 115V 230V 1 PH Unit 01 C45 C75 C150 02xH 01 21 ...

Страница 7: ...e terminal for proper unit voltage 2 Omit BL 25 BL 30 for 0 10V Signal Control Wire BL 25 to TB39 1 and BL 30 to TB40 1 for low speed Wire BL 25 to TB39 2 BL 30 to TB40 2 for high speed Mini Ventilator W Factory Installed Options 115V 230V 1 PH Unit 01 C45 C75 C150 02xE 01 21 ...

Страница 8: ...ation If blower motor fans are running backwards de energize power to the unit then swap reversing plug on motors to change direction Re check Perform all start up procedures outlined in the installation manual shipped with the unit Fill in the Start Up Information as outlined on the opposite side of this sheet Provide owner with information packet Explain the thermostat and unit operation START U...

Отзывы: