background image

 

 

Appendix A: Connectors and Connection Media 

1000BASE-T/100BASE-TX/10BASE-T Ports 

The 1000BASE-T/100BASE-TX/10BASE-T is a port that supports adaptation of three rates, and automatic MDI/MDIX 

Crossover at these three rates. 

The 1000BASE-T complies with IEEE 802.3ab, and uses the cable of 100-ohm Category-5 or Supper Category-5 UTP or 

STP, which can be up to 100 m. 

The 1000BASE-T port uses four pairs of wires for transmission, all of which must be connected. Figure A-1 shows the 

connections of the twisted pairs used by the 1000BASE-T port. 

Figure A-1 Four Twisted Pairs of the 1000BASE-T 

Straight-Through 

Crossover 

Switch                                        Switch 

Switch                                          Switch 

1 TP0 + 

  1 TP0 + 

1 TP0 +                                          1 TP0 + 

2 TP0 - 

  2 TP0 - 

2 TP0 -                                          2 TP0 - 

3 TP1 + 

  3 TP1 + 

3 TP1 +                                          3 TP1 + 

6 TP1 - 

  6 TP1 - 

6 TP1 -                                          6 TP1 - 

4 TP2 + 

  4 TP2 + 

4 TP2 +                                          4 TP2 + 

5 TP2 - 

  5 TP2 - 

5 TP2 -                                          5 TP2 - 

7 TP3 + 

  7 TP3 + 

7 TP3 +                                          7 TP3 + 

8 TP3 - 

  8 TP3 - 

8 TP3 -                                          8 TP3 - 

In addition to the above cables, the 100BASE-TX/10BASE-T can also use 100-ohm Category-3, 4, 5 cables for 10 Mbps, 

and 100-ohm Category-5 cables for 100 Mbps, both of which can be up to 100 m. Figure A-2 shows the pinouts of the 

100BASE-TX/10BASE-T. 

Figure A-2 Pinouts of the 100BASE-TX/10BASE-T 

Pin 

Socket 

Plug 

Input Receive Data+ 

Output Transmit Data+ 

Input Receive Data- 

Output Transmit Data- 

Output Transmit Data+ 

Input Receive Data+ 

Output Transmit Data- 

Input Receive Data- 

4, 5, 7, 8 

Not Used 

Not Used 

Figure A-3 shows the straight-through and crossover cable connections for the 100BASE-TX/10BASE-T. 

Figure A-3 Connections of the Twisted Pairs of the 100BASE-TX/10BASE-T 

 

Содержание RG-S2928G-12P

Страница 1: ...RG S2900G E Series Switch Hardware Installation and Reference Guide V1 25...

Страница 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Страница 3: ...taining Technical Assistance Ruijie Networks Website http www ruijienetworks com Service Email service_rj ruijienetworks com Technical Support http www ruijienetworks com service aspx Technical Suppor...

Страница 4: ...s Model 10 100 1000 Base T Adaptive Ethernet Port SFP Port Console Port Extension Module Slot RG S2928G E 24 4 1 N A RG S2952G E 48 4 1 N A RG S2928G 12P 24 4 1 N A RG S2928G 24P 24 4 1 N A The four S...

Страница 5: ...ge 90 V to 264 V Frequency 50 60 Hz Rated current 2A HVDC input Maximum voltage range 192 V to 290 V Rated current 0 2 A to 0 12 A EEE Not supported on the RG S2928G E V1 00 and later Supported on the...

Страница 6: ...rnet adaptive ports and four SFP ports Figure 1 1 shows the appearance of the RG S2928G E Figure 1 1 Appearance of the RG S2928G E Front Panel Figure 1 2 Front Panel of the RG S2928G E Note 1 USB2 0 p...

Страница 7: ...cord 10A power cord Heat Dissipation The RG S2928G E full gigabit switch is designed with no fans To ensure good dissipation sufficient space 10 cm distance from both sides and the back panel of the c...

Страница 8: ...G S2928G E V2 00 and later support 100Base FX 25F 28F Off The port is NOT connected Solid green The port is connected Blinking The port is transmitting or receiving data 1 2 RG S2952G E Technical Spec...

Страница 9: ...ximum voltage range 192 V to 290 V Rated current 0 3 A to 0 17 A EEE Not supported on the RG S2952G E V1 00 and later Supported on the RG S2952G E V2 00 and later PoE Not supported Power Consumption L...

Страница 10: ...4 shows the appearance of the RG S2952G E Figure 1 4 Appearance of the RG S2952G E Front Panel Figure 1 5 Front Panel of the RG S2952G E Note 1 USB2 0 port 2 RJ45 console port 3 RJ45 10 100 1000Base T...

Страница 11: ...nt 1 5 A Power cord 10A power cord HVDC input Maximum voltage range 192 V to 290 V Rated current 0 3 A to 0 17 A Power cord 10A power cord Heat Dissipation The RG S2952G E full gigabit switch adopts f...

Страница 12: ...1 48 Off The port is NOT connected Solid green The port is connected at 1000Mbps Solid yellow The port is connected at 100 10Mbps Blinking The port is transmitting or receiving data 100 Base FX 1000 B...

Страница 13: ...X 1000 Base T 100 Base FX and 2 5 G stacked SFP module USB Port One Type A USB2 0 interface Power Supply AC input Rated voltage range 100 V to 240 V Maximum voltage range 90 V to 264 V Frequency 50 60...

Страница 14: ...e RG S2928G 12P Front Panel Figure 1 10 Front Panel of the RG S2928G 12P Note 1 USB2 0 port 2 RJ45 console port 3 System status indicator 4 10 100 1000Base T adaptive Ethernet port indicator 5 RJ45 10...

Страница 15: ...current 3 A Power cord 10A power cord HVDC input Maximum voltage range 192 V to 290 V Rated current 2 A to 1 5 A Power cord 10A power cord Heat Dissipation The RG S2928G 12P switch adopts axial fans f...

Страница 16: ...tem is being initialized Solid green The system is operational Solid yellow System over temperature warning Solid red Serious over temperature the system will stop working forcibly by itself Or the fa...

Страница 17: ...Base T Mini GBIC GT 2 5 G stack module GE SFP STACK1 6M The supported module type may change at any time Contact us for the detailed change information SFP Port Support 1000 Base X 1000 Base T 100 Bas...

Страница 18: ...pport adjustment of fan speed and warning of fan troubles Temperature Warning Supported EMC Standards GB9254 1998 Safety Standards GB4943 2001 Dimensions W x D x H 440 mm x 260 mm x 43 6 mm Weight Les...

Страница 19: ...hover button By default the switch port indicator indicates the switched mode You can press this button to switch the status of indicator between switched mode and PoE mode Back Panel Figure 1 15 Back...

Страница 20: ...ly of the RG S2928G 24P switch is designed to support the IEEE802 3af and 802 3at standards It uses Alternative A that is uses pins 1 2 and 3 6 to transmit power LED Indicators Indicator Faceplate Mar...

Страница 21: ...1 24 Off No PoE power supply Solid green PoE is operational Solid yellow Abnormal PoE power supply 100Base FX 1000Base X Stack port indicator 25F 28F Off The port is NOT connected Solid green The port...

Страница 22: ...e turn off all power supplies and dismantle all power modules 2 1 3 Electric Safety Observe local regulations and specifications when performing electric operations Relevant operators must be qualifie...

Страница 23: ...rable life of the equipment the installation site must meet the following requirements 2 2 1 Ventilation Requirements For the RG S2900G E series you must ensure that sufficient space 10 cm distance fr...

Страница 24: ...reat to the running of the equipment The indoor dust falling on the equipment may be adhered by the static electricity causing bad contact of the metallic joint Such electrostatic adherence may occur...

Страница 25: ...is for the stable and reliable operation of the RG S2900G E series It is the chief condition to prevent lightning stroke and resist interference Please carefully check the grounding conditions on the...

Страница 26: ...depending on the type of the transmission path When the energy often RF energy from a component arrives at a sensitive component via the space the energy is known as radiated interference The interfer...

Страница 27: ...e 2 4 List of Installation Tools Common tools Philips screwdriver flathead screwdriver related electric cables and optical cables bolts diagonal pliers straps Special tools Anti static tools Meters Mu...

Страница 28: ...ing points Whether ventilation requirements are met for the switch Whether the requirements of temperature and humidity are met for the switch Whether power cables are already laid out and whether the...

Страница 29: ...ry electromagnetic shielding should be adopted For example use interface cables to shield cables 100 meter network cables should be laid inside the equipment room and outdoor cabling of such cables is...

Страница 30: ...that the ground line is connected Check that the cables and power input cables are correctly connected Check that the 100 meter cables are laid out inside the equipment room In the case of external c...

Страница 31: ...l port of the PC Step 2 Connect the end of the console cable with RJ45 to the console port of the switch Setting HyperTerminal Parameters Step 1 Start the PC and run the terminal simulation program on...

Страница 32: ...layed Choose the serial port used currently in the column use when connecting Figure 4 3 After choosing the serial port click OK to display the serial port parameter setting interface set the baud rat...

Страница 33: ...rminal is started and the parameter settings are correct 4 2 2 Checking after Program Startup Recommended After power on you are recommended to perform the following checks to ensure the normal operat...

Страница 34: ...icator is not on after the switch is started The power supply module does not supply power The power cable is in loose contact Check whether the power socket at the equipment room is normal and whethe...

Страница 35: ...The PoE port cannot be powered The PoE function is not enabled The connected twisted pair is faulty The PD that is the powered device for example AP connected to the port does not comply with the 802...

Страница 36: ...1 TP0 1 TP0 2 TP0 2 TP0 2 TP0 2 TP0 3 TP1 3 TP1 3 TP1 3 TP1 6 TP1 6 TP1 6 TP1 6 TP1 4 TP2 4 TP2 4 TP2 4 TP2 5 TP2 5 TP2 5 TP2 5 TP2 7 TP3 7 TP3 7 TP3 7 TP3 8 TP3 8 TP3 8 TP3 8 TP3 In addition to the...

Страница 37: ...OTD 3 IRD 6 OTD 6 IRD 6 OTD 6 IRD 2 Optical Fiber Connection For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The...

Страница 38: ...sity of Received Light dbm MAX Standard Complian ce MINI GBIC S X MM850 850 Multi mode fiber 62 5 62 5 50 0 50 0 160 200 400 500 220 m 275 m 500 m 550 m 4 17 IEEE802 3 MINI GBIC L X SM1310 1310 Multi...

Страница 39: ...as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the residential area Otherwise the machine room should meet t...

Отзывы: