Appendix C Site Selection 

 

The machine room should be at least 5km away from the heavy pollution source such as the smelter, coal mine and 

thermal power plant, 3.7km away from the medium pollution source such as the chemical industry, rubber industry 

and electroplating industry, and 2km away from the light pollution source such as the food manufacturer and leather 

plant. If the pollution source is unavoidable, the machine room should be located on the windward side of the 

pollution source perennially with advanced protection. 

 

The machine room should be at least 3.7km away from the sea or salt lake. Otherwise, the machine room must be 

sealed, with air conditioner installed for temperature control. Saline soil cannot be used for construction. Otherwise, 

you should select devices with advanced protection against severe environment. 

 

Do not build the machine room in the proximity of livestock farms. Otherwise, the machine room should be located 

on the windward side of the pollution source perennially. The previous livestock house or fertilizer warehouse cannot 

be used as the machine room.   

 

The machine room should be firm enough to withstand severe weather conditions such as windstorm and heavy rain 

as well as away from dust. If the dust is unavoidable, keep the door and window away from the pollution source. 

 

The machine room should be away from the residential area. Otherwise, the machine room should meet the 

construction standard in terms of noise. 

 

Make sure the air vent of the machine room is away from the sewage pipe, septic tank, and sewage treatment tank. 

Keep the machine room under positive pressure to prevent corrosive gas from entering the machine room to corrode 

components and circuit boards. Keep the machine room away from industrial boiler and heating boiler. 

 

The machine room had better be on the second floor or above. Otherwise, the machine room floor should be 600mm 

higher than the highest flood level ever recorded. 

 

Make sure there are no cracks or holes in the wall and floor. If there are cable entries in the wall or window, take 

proper sealing measures. Ensure that the wall is flat, wear-resistant, and dust-free, which should be up to the 

standard for flame retarding, soundproofing, heat absorption, dust reduction, and electromagnetic shielding. 

 

Keep the door and the window closed to make the machine room sealed. 

 

The steel door is recommended for soundproofing. 

 

Sulfur-containing materials are forbidden. 

 

Pay attention to the location of the air conditioner. Keep the air conditioner from blowing wind straight toward the 

device or blowing water drops from the window or air vent toward the device. 

 

 

Содержание RG-S2928G-12P

Страница 1: ...RG S2900G E Series Switch Hardware Installation and Reference Guide V1 25...

Страница 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Страница 3: ...taining Technical Assistance Ruijie Networks Website http www ruijienetworks com Service Email service_rj ruijienetworks com Technical Support http www ruijienetworks com service aspx Technical Suppor...

Страница 4: ...s Model 10 100 1000 Base T Adaptive Ethernet Port SFP Port Console Port Extension Module Slot RG S2928G E 24 4 1 N A RG S2952G E 48 4 1 N A RG S2928G 12P 24 4 1 N A RG S2928G 24P 24 4 1 N A The four S...

Страница 5: ...ge 90 V to 264 V Frequency 50 60 Hz Rated current 2A HVDC input Maximum voltage range 192 V to 290 V Rated current 0 2 A to 0 12 A EEE Not supported on the RG S2928G E V1 00 and later Supported on the...

Страница 6: ...rnet adaptive ports and four SFP ports Figure 1 1 shows the appearance of the RG S2928G E Figure 1 1 Appearance of the RG S2928G E Front Panel Figure 1 2 Front Panel of the RG S2928G E Note 1 USB2 0 p...

Страница 7: ...cord 10A power cord Heat Dissipation The RG S2928G E full gigabit switch is designed with no fans To ensure good dissipation sufficient space 10 cm distance from both sides and the back panel of the c...

Страница 8: ...G S2928G E V2 00 and later support 100Base FX 25F 28F Off The port is NOT connected Solid green The port is connected Blinking The port is transmitting or receiving data 1 2 RG S2952G E Technical Spec...

Страница 9: ...ximum voltage range 192 V to 290 V Rated current 0 3 A to 0 17 A EEE Not supported on the RG S2952G E V1 00 and later Supported on the RG S2952G E V2 00 and later PoE Not supported Power Consumption L...

Страница 10: ...4 shows the appearance of the RG S2952G E Figure 1 4 Appearance of the RG S2952G E Front Panel Figure 1 5 Front Panel of the RG S2952G E Note 1 USB2 0 port 2 RJ45 console port 3 RJ45 10 100 1000Base T...

Страница 11: ...nt 1 5 A Power cord 10A power cord HVDC input Maximum voltage range 192 V to 290 V Rated current 0 3 A to 0 17 A Power cord 10A power cord Heat Dissipation The RG S2952G E full gigabit switch adopts f...

Страница 12: ...1 48 Off The port is NOT connected Solid green The port is connected at 1000Mbps Solid yellow The port is connected at 100 10Mbps Blinking The port is transmitting or receiving data 100 Base FX 1000 B...

Страница 13: ...X 1000 Base T 100 Base FX and 2 5 G stacked SFP module USB Port One Type A USB2 0 interface Power Supply AC input Rated voltage range 100 V to 240 V Maximum voltage range 90 V to 264 V Frequency 50 60...

Страница 14: ...e RG S2928G 12P Front Panel Figure 1 10 Front Panel of the RG S2928G 12P Note 1 USB2 0 port 2 RJ45 console port 3 System status indicator 4 10 100 1000Base T adaptive Ethernet port indicator 5 RJ45 10...

Страница 15: ...current 3 A Power cord 10A power cord HVDC input Maximum voltage range 192 V to 290 V Rated current 2 A to 1 5 A Power cord 10A power cord Heat Dissipation The RG S2928G 12P switch adopts axial fans f...

Страница 16: ...tem is being initialized Solid green The system is operational Solid yellow System over temperature warning Solid red Serious over temperature the system will stop working forcibly by itself Or the fa...

Страница 17: ...Base T Mini GBIC GT 2 5 G stack module GE SFP STACK1 6M The supported module type may change at any time Contact us for the detailed change information SFP Port Support 1000 Base X 1000 Base T 100 Bas...

Страница 18: ...pport adjustment of fan speed and warning of fan troubles Temperature Warning Supported EMC Standards GB9254 1998 Safety Standards GB4943 2001 Dimensions W x D x H 440 mm x 260 mm x 43 6 mm Weight Les...

Страница 19: ...hover button By default the switch port indicator indicates the switched mode You can press this button to switch the status of indicator between switched mode and PoE mode Back Panel Figure 1 15 Back...

Страница 20: ...ly of the RG S2928G 24P switch is designed to support the IEEE802 3af and 802 3at standards It uses Alternative A that is uses pins 1 2 and 3 6 to transmit power LED Indicators Indicator Faceplate Mar...

Страница 21: ...1 24 Off No PoE power supply Solid green PoE is operational Solid yellow Abnormal PoE power supply 100Base FX 1000Base X Stack port indicator 25F 28F Off The port is NOT connected Solid green The port...

Страница 22: ...e turn off all power supplies and dismantle all power modules 2 1 3 Electric Safety Observe local regulations and specifications when performing electric operations Relevant operators must be qualifie...

Страница 23: ...rable life of the equipment the installation site must meet the following requirements 2 2 1 Ventilation Requirements For the RG S2900G E series you must ensure that sufficient space 10 cm distance fr...

Страница 24: ...reat to the running of the equipment The indoor dust falling on the equipment may be adhered by the static electricity causing bad contact of the metallic joint Such electrostatic adherence may occur...

Страница 25: ...is for the stable and reliable operation of the RG S2900G E series It is the chief condition to prevent lightning stroke and resist interference Please carefully check the grounding conditions on the...

Страница 26: ...depending on the type of the transmission path When the energy often RF energy from a component arrives at a sensitive component via the space the energy is known as radiated interference The interfer...

Страница 27: ...e 2 4 List of Installation Tools Common tools Philips screwdriver flathead screwdriver related electric cables and optical cables bolts diagonal pliers straps Special tools Anti static tools Meters Mu...

Страница 28: ...ing points Whether ventilation requirements are met for the switch Whether the requirements of temperature and humidity are met for the switch Whether power cables are already laid out and whether the...

Страница 29: ...ry electromagnetic shielding should be adopted For example use interface cables to shield cables 100 meter network cables should be laid inside the equipment room and outdoor cabling of such cables is...

Страница 30: ...that the ground line is connected Check that the cables and power input cables are correctly connected Check that the 100 meter cables are laid out inside the equipment room In the case of external c...

Страница 31: ...l port of the PC Step 2 Connect the end of the console cable with RJ45 to the console port of the switch Setting HyperTerminal Parameters Step 1 Start the PC and run the terminal simulation program on...

Страница 32: ...layed Choose the serial port used currently in the column use when connecting Figure 4 3 After choosing the serial port click OK to display the serial port parameter setting interface set the baud rat...

Страница 33: ...rminal is started and the parameter settings are correct 4 2 2 Checking after Program Startup Recommended After power on you are recommended to perform the following checks to ensure the normal operat...

Страница 34: ...icator is not on after the switch is started The power supply module does not supply power The power cable is in loose contact Check whether the power socket at the equipment room is normal and whethe...

Страница 35: ...The PoE port cannot be powered The PoE function is not enabled The connected twisted pair is faulty The PD that is the powered device for example AP connected to the port does not comply with the 802...

Страница 36: ...1 TP0 1 TP0 2 TP0 2 TP0 2 TP0 2 TP0 3 TP1 3 TP1 3 TP1 3 TP1 6 TP1 6 TP1 6 TP1 6 TP1 4 TP2 4 TP2 4 TP2 4 TP2 5 TP2 5 TP2 5 TP2 5 TP2 7 TP3 7 TP3 7 TP3 7 TP3 8 TP3 8 TP3 8 TP3 8 TP3 In addition to the...

Страница 37: ...OTD 3 IRD 6 OTD 6 IRD 6 OTD 6 IRD 2 Optical Fiber Connection For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The...

Страница 38: ...sity of Received Light dbm MAX Standard Complian ce MINI GBIC S X MM850 850 Multi mode fiber 62 5 62 5 50 0 50 0 160 200 400 500 220 m 275 m 500 m 550 m 4 17 IEEE802 3 MINI GBIC L X SM1310 1310 Multi...

Страница 39: ...as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the residential area Otherwise the machine room should meet t...

Отзывы: