background image

5

I N S T A L L A T I O N

The installation instructions provide a general guideline for the installation and wiring of the heater.  

All applicable codes must be adhered to.

M E C H A N I C A L

L O C A T I O N

For optimum heating, the heater should be installed as follows:
  1.  There are no obstructions that may impede the heater’s air  

 

 

   

inlet or discharge. 

  2.  The air discharge is directed into open areas and not at   

 

 

   

occupants.

  3.  The air discharge is not directed at a thermostat.
  4.  The air discharge is directed across areas of heat loss, such  

 

 

   

as doors and windows (see Figure 2).

  5.  The air discharge is directed along and at a slight angle   

 

 

   

toward exterior walls (see Figure 2).

  6.  If equipment freeze protection is important, direct air  

 

 

 

   

discharge at equipment.

  7.  Air discharge streams support each other and create a    

 

 

   

circular air flow.  It is not required that the heater’s air  

 

 

 

   

throw reaches the next heater (see Figure 2).

HEATER LOCATIONS

EXTERIOR WALL

EXTERIOR 
WALL

FIGURE 2

T R O U B L E S H O O T I N G   T I P S

1.0  

Heater is not operating

 

1.1  Check all fuses in heater control box.

 

1.2  Check remote disconnect switch and circuit breaker.

 

1.3  Check voltage supplied to the heater – refer to the heater data plate for voltage requirements.

 

1.4  Check thermostat by turning it and check continuity with a multimeter.

 

1.5  Check the condition of the disconnect switch if the heater is so equipped. Measure continuity through the disconnect  
       by engaging the switch.

 

1.6  Verify that there is a jumper wire present between terminals 5 and 6 on the terminal block located in the control box.

2.0  

Contactor is chattering

 

2.1  Check supply voltage.

 

2.2  Check wiring connections. Tighten all loose electrical connections.

 

2.3  Check thermostat for continuity (See 1.4). If thermostat does not break continuity replace thermostat.

3.0  

Contactor is burned or welded

 

3.1  Check the contactor for burn marks and blackening. Replace the contactor.

 

3.2  Check incoming power to the heater to ensure there are no voltage fluctuations.

4.0  

Heat exchanger is dirty

 

4.1  Clean the heat exchanger using compressed air. 

5.0.   PRV has released

 

5.1  If there are signs that the PRV has released fluid, PRV indicator is broken, blackening around the PRV exit hole, or 

 

       there are fluid stains visible on the top louver, shut the unit down immediately. 

 

5.2  Check for restricted air flow, bad motor, broken thermostat or malfunctioned high limit.

6.0  

Heater is cold on top and warm on bottom

 

6.1  The core may have lost its vacuum. Check the PRV for signs of loss of fluid and verify that the PRV label indicator is 

 

       not broken. If PRV has released, send the unit in for repair or replace the core. 

 

6.2  If the PRV does not indicate loss of fluid, the heater should operate normally. Check for loss of fluid on a weekly basis 

 

       as a minimum.

 

6.3  The ambient temperature may be too low. If the ambient temperature is very cold the top of the core will be colder  
       than the bottom – this is normal. 

7.0  

unit cycles on high limit – unit turns on and turns off within less than 5 minutes.

 

7.1  Check and see if the PRV has released fluid. Core may have lost most or all of its fluid. If PRV has released, send the 

 

        unit in for repair or replace core.

 

7.2  The core may be dirty, fan may not be working or may be turning the wrong way (the fan must rotate clockwise as 

 

        seen from the front of the unit) objects may be stuck in the heat exchanger for drying or warming up – remove any 

 

        items from the exchanger.

8.0  

The ground Fault Interrupter (gFI) trips on the main panel, or heater blows fuses.

 

8.1  Check that you have a fuse of the proper amperage rating.

 

8.2  Check for loose or frayed wiring.

 

8.3  If condition is not observable, send heater in for repair.

 

8.4  Change sensitivity of GFI.

9.0  

The fan is turning but very little air comes from the front of the heater.

 

9.1  Check fan rotation and ensure that the fan turns clockwise as seen from the front of the heater. Refer to the Installation  
       section below for more information.

 

9.2  Check motor winding resistance and verify that they are balanced.

 

9.3  Check fan blade set screws to ensure fan blade is not loose on the motor shaft.

Содержание FX5-220150-025

Страница 1: ...Core are registered trademarks of CCI Thermal Technologies Inc Copyright 2010 All rights reserved approved Locations The Electric Forced Air Heaters are cULus listed certified for the following locations class i divisions 1 2 groups c d class ii division 1 groups e f g class ii division 2 groups f g Class I Zones 1 2 Groups IIA IIB Temperature Code T3B 165 C 329 F 50 Hz 60 Hz Models For details of...

Страница 2: ... Maintenance Grid Regular Service Severe Service Annual Start Up 1 Month 3 Month 12 Month Annual Start Up 1 Month 3 Month 12 Month Clean Finned Tubes Fan Fan Guard Motor Louvers Remove dust using compressed air Do not Spray with water or solvents Do not immerse in water or solvents X X X Electrical Check all terminal connections and conductors Tighten loose connections Replace conductors with dama...

Страница 3: ...eplaced A factory supplied exchange core can be shipped immediately from stock Refer to the Repair and Replacement section for details Check all enclosures Interior of enclosures must be clean dry and free of foreign materials Threaded covers must be installed and hand tight Note Enclosure joints are metal to metal Do not use gasket material or sealant in joints A grease is applied to the joints a...

Страница 4: ...igh limit disabled or disconnected from the control circuit 9 Venting pressure of the pressure relief valve is factory set Do not tamper with lock nut 10 Do not tamper or remove warning label indicator on the PRV 11 Operate the heater only while it is permanently mounted in an upright position Refer to the Installation Mechanical section for details 12 Heater must be kept clean When operating in a...

Страница 5: ...e are no voltage fluctuations 4 0 Heat exchanger is dirty 4 1 Clean the heat exchanger using compressed air 5 0 PRV has released 5 1 If there are signs that the PRV has released fluid PRV indicator is broken blackening around the PRV exit hole or there are fluid stains visible on the top louver shut the unit down immediately 5 2 Check for restricted air flow bad motor broken thermostat or malfunct...

Страница 6: ...me delay fuses for maximum safety Unless stated otherwise in your local code fuse size shall be 125 of line current or next size larger F ield W iring 1 The supply conductors ground conductor and room thermostat conductors see point 2 page 5 all pass through the 1 NPT opening see Figure 6 and are to be wired into the control enclosure see Figure 7A 2 Heater may be supplied with a factory installed...

Страница 7: ... T STAT c To reduce risk of ignition of hazardous atmospheres conduit runs must have a sealing fitting connected within 18 inches 457 mm Factory installed conduits require no further sealing Integral Disconnect is sealed at factory 4 The internal grounding terminal in the control enclosure or in the integral disconnect enclosure when this option is provided shall be used as the equipment grounding...

Страница 8: ... 1 2 3 4 5 6 2 3 4 6 5 3 PHASE WIRING SCHEMATIC 3 WAY SWITCH AND CONTINUOUS FAN OPTION A B C A B C OPTIONAL 3 WAY SWITCH FAN B OFF AUTO A C ELEMENTS 380 415 60HZ 208 230 240 480 800 60HZ OPTIONAL INTEGRAL DISCONNECT L2 L3 L1 OPTIONAL PILOT LIGHT OPTIONAL ROOM THERMOSTAT PCB FUSE OPTIONAL REDUNDANT TEMPERATURE HIGH LIMIT AUTO RESET TEMPERATURE HIGH LIMIT AMBIENT AIR AUTO RESET TEMPERATURE HIGH LIMI...

Страница 9: ... 23 1 3 1 0 22 200 33 3 41 6 8 45 24 3 13 5 9535 3618 FX5 415350 037 700 415 3 7 3 0 7 3 510 5 1 6 4 16 10 16 7 9 3 9537 3618 FX5 415350 075 700 415 7 5 3 0 7 7 240 10 4 13 0 14 15 33 9 18 8 9539 3618 FX5 415350 149 1450 415 14 9 3 0 7 14 500 20 7 25 9 10 30 32 5 18 1 9541 3618 FX5 415350 224 3000 415 22 4 3 1 0 21 800 31 2 39 0 8 40 23 6 13 1 9543 3618 FX5 440350 042 700 440 4 2 3 0 7 3 950 5 5 6...

Страница 10: ...15 0 14 15 37 2 20 7 10417 10557 FX5 480360 150 480 15 0 3 0 7 14 400 18 0 22 5 10 25 27 1 15 1 10426 10557 FX5 480360 200 480 20 0 3 0 7 19 400 24 1 30 1 8 35 36 1 20 1 10218 10557 FX5 480360 250 480 25 0 3 1 0 24 200 30 1 37 6 8 40 45 2 25 1 10430 10557 FX5 480360 300 480 30 0 3 1 0 29 200 36 1 45 1 6 50 26 4 14 6 10431 10558 FX5 480360 350 480 35 0 3 1 0 34 200 42 1 52 6 6 60 30 7 17 1 10432 10...

Страница 11: ...low watt density high grade metal sheathed elements Temperature High Limit Automatic reset type snap action bimetal open on temperature rise Rated 100 000 cycles at 10 amps handles 0 128 amps Control Circuit 120 Volts 0 128 amps 15VA Grounded Optional Built in Thermostat Explosion proof 2 C to 28 C 36 F to 82 F Optional Built in Disconnect Switch DS5 for use only on heaters with total current not ...

Страница 12: ...ng life low watt density high grade metal sheathed elements Temperature High Limit Automatic reset type snap action bimetal open on temperature rise Rated 100 000 cycles at 10 amps handles 0 128 amps Control Circuit 120 Volts 0 128 amps 15VA Grounded Optional Built in Thermostat Explosion proof 2 C to 28 C 36 F to 82 F Optional Built in Disconnect Switch DS5 for use only on heaters with total curr...

Страница 13: ...N BUS BAR CONFIGURATION BUS BAR CONFIGURATION ALL 1 PHASE MODELS FOR ALL 3 PHASE EXCEPT 380 50 HERTZ 3 PHASE 380 VOLT 50 HERTZ MODELS ONLY HEATER ASSEMBLY DIAGRAM CONTROL ENCLOSURE ASSEMBLY DIAGRAM HIGH LIMIT ASSEMBLY DIAGRAM ...

Страница 14: ... Motor Mount 13 Painted 3788 S S 9111 Painted 3788 S S 9111 Painted 3788 S S 9111 Bracket Motor Mount Left 14 3737 Emersion Motors 4590 Baldor Marathon Motors Coupling Motor Mount 15 9500 3813 10389 Conduit Motor 16 5371 5371 5371 Cover Thermostat Enclosure 17 3813 3812 3813 Conduit Control Enclosure 18 9314 9315 9316 Conduit Element Enclosure 19 9679 9679 9679 Enclosure Element 20 3510 3510 3510 ...

Страница 15: ...it 1 located between motor junction box and control enclosure by turning it in the direction illustrated see Figure 14 Note conduits 1 and 2 are not interchangeable and have left hand threads on one end this end is indicated by a machined groove 3 Remove the 2 piece fan guard assembly see Figure 15 4 Lift the motor assembly off the motor mount 5 Before removing the fan measure and record the locat...

Страница 16: ...lied contactor of the same rating T ransformer 1 Replace with a factory supplied transformer of the same rating 2 On the new transformer select primary wires to match heater voltage Ensure that the correct transformer secondary lead is grounded see Figure 9 Individually terminate all unused wires using closed end connectors F use Replace fuse with one of the same type and rating as indicated on P ...

Страница 17: ... We will provide replacement parts free of charge as necessary to restore any unit to operating condition provided that the inoperative parts be returned to us freight prepaid and that the replacement parts be accepted freight collect 2 The complete heater may be returned to our plant for repair or replacement at our discretion provided that all related freight costs be borne by the customer 3 Cor...

Отзывы: