background image

15

{

REPAIR & REPLACEMENT

1.    After repairing any component:

  

a. check that electrical connections are correct and secure (see Figure 9),

  

b. remove any foreign material from enclosures,

  

c. install and secure all covers,

  

d. ensure that all fasteners are tight,

  

e. remove all foreign objects from heater, and

  

f.  ensure air exits through louvers and fan rotates counterclockwise when 

  

    viewed from rear of heater (see Figure 14).

C O R E

The heater core is vacuum charged and not field repairable. 
For core removal:
1. 

Remove cabinet bottom and element enclosure cover. 

2.  Disconnect all wires entering element enclosure (see Figure 10).

3. 

Slightly  loosen  all  cabinet  bolts  shown  in  Figure  10,  to  prevent  the  core 
from

 

binding.

4. 

With an assistant supporting the weight of the core, remove the 3 core

 

mounting bolts. Carefully lower the core out of the cabinet 

 

(see Figure 11).

5. 

To  return  core  to  factory,  use  crate  supplied  with  exchange  core  to 
protect

 

the element terminals and plate threads.

6. 

To reinstall, lift the core up into cabinet while an assistant guides the

 

element wires into the element enclosure conduit.

7. 

Position the core and tighten the 3 core mounting bolts. Tighten the

 

remaining cabinet bolts.

T E M P E R AT U R E   H I G H - L I M I T

1. 

Remove temperature high-limit assembly and clean the inside of the

 

thermowell (see Figure 12). A clean thermowell will ensure good thermal

 

contact.

2. 

Use only a factory supplied temperature high-limit to ensure safe operation.

 

(refer  to  the  instructions  that  accompany  the  replacement  Temperature   

High-Limit Kit).

3. 

Reinstall the temperature high-limit assembly with the snap ring and spring

 

into the thermowell without damaging the insulating tube. Secure in place

 

with the cotter pin (see Figure 13).

M O TO R ,   FA N   &   FA N   G U A R D

1. 

Remove bolts holding the motor to the motor mount.  On units with a built

 

in thermostat, remove the bolts on the back of the thermostat enclosure.

2. 

Remove  conduit  #1  located  between  motor  junction   box  and  control 

 

enclosure  by turning  it  in the direction  illustrated  (see Figure 14). 

 

Note  conduits #1 and #2 are not interchangeable and have left hand threads on

 

one end, this end is indicated by a machined groove.

3.  Remove the 2 piece fan guard assembly (see Figure 15).

4. 

Lift the motor assembly off the motor mount.

5. 

Before removing the fan, measure and record the location of the fan hub on the

 

motor shaft (see Figure 16). If difficult to remove, use a gear puller on the fan hub.

6. 

To reassemble, place motor assembly onto motor mount and fasten the fan guard

 

to cabinet.

7. 

Simultaneously engage and tighten both ends of conduit #1 into enclosures.

 

Leave a 1/16” to 3/16” (1.6 to 4.8 mm) gap between the motor and fan guard 

 

(see Figure 16). Adjust conduit #2 to center the fan in the shroud.

8. 

To ensure a minimum 5 thread engagement, threaded ends of conduits must

 

protrude a minimum of 1/16” (1.6mm) into enclosures. The groove on conduit #2

 

must not be more than 7/8” (22mm) from motor coupling (see Figure 14).

9. 

Bolt motor to motor mount.  Manually spin the fan blade to ensure fan rotates freely.

10.  Air must exit through louvers and fan must rotate counterclockwise when viewed

 

from rear of heater (see Figure 14).

FIGURE 14

FIGURE 13

FIGURE 12

FIGURE 11

FIGURE 10

}

Loosen 
bolts 
only, 
do not 
remove.

Loosen 
bolts 
only, 
do not 
remove.

Element 
Enclosure

Remove  this 
core  mounting 
b o l t   &   t w o 
others  on  the 
opposite side.

Rotation

Air inlet

Conduit #2

Conduit #1

Remove

Install

7/8” (22mm)
(From groove to 
face of coupling)

Thermowell

Control 
Enclosure

Conduit
Junction
Enclosure

WARNING

Disconnect heater from power supply at integral disconnect or fuse box before 

opening enclosures or servicing heater. Lock the switch in the “OFF” (open) 

position and/or tag the switch to prevent unexpected power application. 

IF INTEGRAL DISCONNECT IS BEING SERVICED, verify that power has 

been disconnected at fuse box or main panel.  Lock the switch in the “OFF” 

(open) position and/or tag the switch to prevent unexpected power application. 

Heater surfaces may be hot.

Remove

Install

3/32”

(2mm)

Drop

Содержание FX5-220150-025

Страница 1: ...Core are registered trademarks of CCI Thermal Technologies Inc Copyright 2010 All rights reserved approved Locations The Electric Forced Air Heaters are cULus listed certified for the following locations class i divisions 1 2 groups c d class ii division 1 groups e f g class ii division 2 groups f g Class I Zones 1 2 Groups IIA IIB Temperature Code T3B 165 C 329 F 50 Hz 60 Hz Models For details of...

Страница 2: ... Maintenance Grid Regular Service Severe Service Annual Start Up 1 Month 3 Month 12 Month Annual Start Up 1 Month 3 Month 12 Month Clean Finned Tubes Fan Fan Guard Motor Louvers Remove dust using compressed air Do not Spray with water or solvents Do not immerse in water or solvents X X X Electrical Check all terminal connections and conductors Tighten loose connections Replace conductors with dama...

Страница 3: ...eplaced A factory supplied exchange core can be shipped immediately from stock Refer to the Repair and Replacement section for details Check all enclosures Interior of enclosures must be clean dry and free of foreign materials Threaded covers must be installed and hand tight Note Enclosure joints are metal to metal Do not use gasket material or sealant in joints A grease is applied to the joints a...

Страница 4: ...igh limit disabled or disconnected from the control circuit 9 Venting pressure of the pressure relief valve is factory set Do not tamper with lock nut 10 Do not tamper or remove warning label indicator on the PRV 11 Operate the heater only while it is permanently mounted in an upright position Refer to the Installation Mechanical section for details 12 Heater must be kept clean When operating in a...

Страница 5: ...e are no voltage fluctuations 4 0 Heat exchanger is dirty 4 1 Clean the heat exchanger using compressed air 5 0 PRV has released 5 1 If there are signs that the PRV has released fluid PRV indicator is broken blackening around the PRV exit hole or there are fluid stains visible on the top louver shut the unit down immediately 5 2 Check for restricted air flow bad motor broken thermostat or malfunct...

Страница 6: ...me delay fuses for maximum safety Unless stated otherwise in your local code fuse size shall be 125 of line current or next size larger F ield W iring 1 The supply conductors ground conductor and room thermostat conductors see point 2 page 5 all pass through the 1 NPT opening see Figure 6 and are to be wired into the control enclosure see Figure 7A 2 Heater may be supplied with a factory installed...

Страница 7: ... T STAT c To reduce risk of ignition of hazardous atmospheres conduit runs must have a sealing fitting connected within 18 inches 457 mm Factory installed conduits require no further sealing Integral Disconnect is sealed at factory 4 The internal grounding terminal in the control enclosure or in the integral disconnect enclosure when this option is provided shall be used as the equipment grounding...

Страница 8: ... 1 2 3 4 5 6 2 3 4 6 5 3 PHASE WIRING SCHEMATIC 3 WAY SWITCH AND CONTINUOUS FAN OPTION A B C A B C OPTIONAL 3 WAY SWITCH FAN B OFF AUTO A C ELEMENTS 380 415 60HZ 208 230 240 480 800 60HZ OPTIONAL INTEGRAL DISCONNECT L2 L3 L1 OPTIONAL PILOT LIGHT OPTIONAL ROOM THERMOSTAT PCB FUSE OPTIONAL REDUNDANT TEMPERATURE HIGH LIMIT AUTO RESET TEMPERATURE HIGH LIMIT AMBIENT AIR AUTO RESET TEMPERATURE HIGH LIMI...

Страница 9: ... 23 1 3 1 0 22 200 33 3 41 6 8 45 24 3 13 5 9535 3618 FX5 415350 037 700 415 3 7 3 0 7 3 510 5 1 6 4 16 10 16 7 9 3 9537 3618 FX5 415350 075 700 415 7 5 3 0 7 7 240 10 4 13 0 14 15 33 9 18 8 9539 3618 FX5 415350 149 1450 415 14 9 3 0 7 14 500 20 7 25 9 10 30 32 5 18 1 9541 3618 FX5 415350 224 3000 415 22 4 3 1 0 21 800 31 2 39 0 8 40 23 6 13 1 9543 3618 FX5 440350 042 700 440 4 2 3 0 7 3 950 5 5 6...

Страница 10: ...15 0 14 15 37 2 20 7 10417 10557 FX5 480360 150 480 15 0 3 0 7 14 400 18 0 22 5 10 25 27 1 15 1 10426 10557 FX5 480360 200 480 20 0 3 0 7 19 400 24 1 30 1 8 35 36 1 20 1 10218 10557 FX5 480360 250 480 25 0 3 1 0 24 200 30 1 37 6 8 40 45 2 25 1 10430 10557 FX5 480360 300 480 30 0 3 1 0 29 200 36 1 45 1 6 50 26 4 14 6 10431 10558 FX5 480360 350 480 35 0 3 1 0 34 200 42 1 52 6 6 60 30 7 17 1 10432 10...

Страница 11: ...low watt density high grade metal sheathed elements Temperature High Limit Automatic reset type snap action bimetal open on temperature rise Rated 100 000 cycles at 10 amps handles 0 128 amps Control Circuit 120 Volts 0 128 amps 15VA Grounded Optional Built in Thermostat Explosion proof 2 C to 28 C 36 F to 82 F Optional Built in Disconnect Switch DS5 for use only on heaters with total current not ...

Страница 12: ...ng life low watt density high grade metal sheathed elements Temperature High Limit Automatic reset type snap action bimetal open on temperature rise Rated 100 000 cycles at 10 amps handles 0 128 amps Control Circuit 120 Volts 0 128 amps 15VA Grounded Optional Built in Thermostat Explosion proof 2 C to 28 C 36 F to 82 F Optional Built in Disconnect Switch DS5 for use only on heaters with total curr...

Страница 13: ...N BUS BAR CONFIGURATION BUS BAR CONFIGURATION ALL 1 PHASE MODELS FOR ALL 3 PHASE EXCEPT 380 50 HERTZ 3 PHASE 380 VOLT 50 HERTZ MODELS ONLY HEATER ASSEMBLY DIAGRAM CONTROL ENCLOSURE ASSEMBLY DIAGRAM HIGH LIMIT ASSEMBLY DIAGRAM ...

Страница 14: ... Motor Mount 13 Painted 3788 S S 9111 Painted 3788 S S 9111 Painted 3788 S S 9111 Bracket Motor Mount Left 14 3737 Emersion Motors 4590 Baldor Marathon Motors Coupling Motor Mount 15 9500 3813 10389 Conduit Motor 16 5371 5371 5371 Cover Thermostat Enclosure 17 3813 3812 3813 Conduit Control Enclosure 18 9314 9315 9316 Conduit Element Enclosure 19 9679 9679 9679 Enclosure Element 20 3510 3510 3510 ...

Страница 15: ...it 1 located between motor junction box and control enclosure by turning it in the direction illustrated see Figure 14 Note conduits 1 and 2 are not interchangeable and have left hand threads on one end this end is indicated by a machined groove 3 Remove the 2 piece fan guard assembly see Figure 15 4 Lift the motor assembly off the motor mount 5 Before removing the fan measure and record the locat...

Страница 16: ...lied contactor of the same rating T ransformer 1 Replace with a factory supplied transformer of the same rating 2 On the new transformer select primary wires to match heater voltage Ensure that the correct transformer secondary lead is grounded see Figure 9 Individually terminate all unused wires using closed end connectors F use Replace fuse with one of the same type and rating as indicated on P ...

Страница 17: ... We will provide replacement parts free of charge as necessary to restore any unit to operating condition provided that the inoperative parts be returned to us freight prepaid and that the replacement parts be accepted freight collect 2 The complete heater may be returned to our plant for repair or replacement at our discretion provided that all related freight costs be borne by the customer 3 Cor...

Отзывы: