Installation requirements
Provide space in an EIA rack with the following minimum and maximum distances between the front and back posts.
NOTE
For 1U and 2U devices, two people are required to install the device in a rack. One person holds the device, while the other screws
in the front and rear "L" brackets.
Note that if chassis depth (L) is less than 40.64 cm (16 in.), the chassis will not fit into a rack with a maximum depth of 81.28 cm (32 in.)
using the universal four-post rack kit. The maximum rack depth for a chassis less than 40.64 cm (16 in.) is 81.28 cm (32 in.) minus the
difference between the chassis depth and 40.64 cm (16 in.). For example, a chassis with a depth (L) of 35.56 cm (14 in.) is 5.08 cm (2
in.) smaller than 40.64 cm (16 in.), so it will install into a rack with a maximum depth of 81.28 cm (32 in.) - 5.08 cm (2 in.) = 76.2 cm (30
in.).
Review the installation and facility requirements for your product before mounting the device. Refer to
on page 22 for more information.
Time and items required
Allow 15 to 30 minutes to complete the installation.
The following items are required to install the device using the Universal Four-Post Rack Kit:
•
#2 Phillips torque screwdriver
•
1/4-inch slotted-blade torque screwdriver
TABLE 7
Space requirements
Chassis with port-side
side vents
Notes
Chassis depth
Minimum rack depth
Maximum rack depth
No
Applicable to port-side and nonport-side flush mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to port-side flush mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to nonport-side flush mounts.
L
L
81.28 cm (32 in.)