background image

 English 

www.ruck.eu

23

pump is put into operation.   A heating coil that has been installed is protected from icing by an 
anti-freeze thermostat.   If the supply air temperature drops below the temperature set on the 
anti-freeze controller, the valves close and the circulating pump runs constantly, the heating valve 
opens and a fault message is given.   The device automatically runs „PRE-RINSING“ until heating 
provides the desired operation temperature.   The unit restarts then automatically.   If the desired 
operating temperature can not be achieved after 20 min., an error message is displayed.   After-
wards, the unit turns itself completely off until the fault is repaired. (see 13.2. Error table F07) 

Cold water coil/cooling unit

 The cold water coil is steplessly regulated with the cooling valve   If cooling is required, the cooling 
valve is opened and at the same time the cooling unit enable output is activated.   
 The minimum switching time for ON and OFF is 5 minutes each, i.e. the cooling unit is switched on 
and off a maximum of six times per hour. 

 Fig.  10

 Fan 

10.2.  Cleaning and care 

 Servicing, troubleshooting and cleaning may only be performed by specialist personnel in 
accordance with this installation and operating manual and the regulations in force. 

 If operated correctly, 

ruck

 products only require a small amount of maintenance. 

 The following work should be performed at regular intervals, in accordance with health and safety 
regulations: 
•  

Check the operation of the control system and safety devices. 

•  

Check electrical connections and wiring for damage. 

•  

Remove any dirt from the fan impeller or impellers and from inside the fan housing in order to 
prevent any unbalance or reduction in output. 

 

»

 Do not use aggressive or easily 

fl

 ammable products for cleaning (impellers/housing).  

 

»

 Preferably only water (not 

fl

 owing water) or mild suds should be used. 

 

»

 The impeller should be cleaned with a cloth or brush. 

 

»

 Never use a high-pressure cleaner. 

 

»

 Balancing clips must not be moved or removed. 

 

»

 The impeller and 

fi

 ttings must not be damaged in any way. 

•  

Check the operation of the bearing with a visual inspection and by checking running noise. 

•  

Check the unit for leaks on the air side. 

•  

Check the circulating heat exchanger to ensure the belt drive is running correctly. 

 Before putting the unit back into operation after maintenance and servicing work, carry out 
a visual inspection as described in Section 7. 

10.  

Maintenance and repair 
10.1.  Important notes 

•  

Electricity warning (hazardous voltage)! 

 

»

   Failure to observe the hazard may result in death, injury or damage to property. 

    Before performing any work on conductive parts, always disconnect the unit completely 

from the electricity supply and make sure that it cannot be switched back on again. 

•  

Never reach into the impeller or other rotating or moving parts. 

 

»

   Failure to observe the hazard may lead to serious injury. 

    Work may only be performed once the impeller has come to a complete halt. 

•  

Caution! Burning hazard. 

 

»

   Failure to observe the hazard may result in personal injury and/or damage to property. 

    Do not touch the surface until the motor and heater have cooled. 

 Maintenance and repairs may only be performed by specialist personnel in accordance with 
this installation and operating manual and the regulations in force. 

 Do not repair defective or damaged units yourself, but report the damage or faults to the 
manufacturer in writing. 

•  

Unauthorized repairs may cause personal injury and / or damage to property, in which case 
the manufacturer‘s guarantee or warranty will not apply. 

Содержание RLI 1200 EC

Страница 1: ...www ruck eu Assembly and Operating Manual English A bl d O ROTOLINE RLI 700 FC RLI 900 FC RLI 1200 FC RLI 1600 FC RLI 2000 FC RLI 700 EC RLI 1200 EC RLI 1600 EC RLI 2000 EC...

Страница 2: ...on can be derived from our information The information given does not release the user from the obligati on of own judgment and verification It must be remembered that our products are subject to a na...

Страница 3: ...Heating Coil 13 6 3 Condensate drainage 13 7 Electrical connection 14 7 1 Overcurrent protection 15 8 Commissioning 15 9 Operation 16 9 1 Control unit 16 9 1 1 Adjustment of the control unit paramete...

Страница 4: ...l Equipment of Machines Part 1 General requirements The manufacturer undertakes to send the special documentation for the partly completed machine electronically to the relevant authority in an indivi...

Страница 5: ...he operating instructions when you pass the product on to third parties 1 1 Rules and regulations 1 2 Guarantee and liability Also observe the generally applicable legal or otherwise binding regulatio...

Страница 6: ...rea 2 3 Personnel qualifications In this manual there are safety instructions before the steps whenever there is a danger of perso nal injury or damage to the equipment The measures described to avoid...

Страница 7: ...e changed or removed Make sure that all electrical connections are either used or covered Commission the product only if it is installed completely The power switch must be always fully functional and...

Страница 8: ...ting or moving parts Failure to observe the hazard may lead to serious injury Work may only be performed once the impeller has come to a complete halt Never clean the internal space with flowing water...

Страница 9: ...egulation Ano ther cooling or DX coil can also be fitted as an option The device has a remote control for controlling and setting the operating parameters The high quality housing consists of a framel...

Страница 10: ...troller 20 Supply air temperature sensor 21 Drip tray 22 Controller board 23 Safety labels 24 Cover for terminal box 25 Terminal Box Duct 26 Extracted air temperature sensor 27 Air filter M5 extract a...

Страница 11: ...r 20 Supply air temperature sensor 21 Drip tray 22 Controller board 23 Safety labels 24 Cover for terminal box 25 Terminal Box Duct 26 Extracted air temperature sensor 27 Air filter M5 extract air 28...

Страница 12: ...standards in force The following points should be noted and followed The foundation must be even and levelled It must not exhibit unevenness or a slope in any direction Suitable foundations are full...

Страница 13: ...zing point of the water The only advantage of the bypass circuit over the admixture circuit arises when the pipe lengths between three way ball valve and wa ter heater are very long Because the pump i...

Страница 14: ...o be placed either left or riht side of the unit see 4 1 For this use the supplied cable glands fittings and cover plate Cables that carry mains voltage must be fastened with the tension relief device...

Страница 15: ...tection is shown in the enclosed wiring diagram 7 1 Overcurrent protection Tabelle 2 Typ Fuse protection RLI 700 FC 3 x 16 A RLI 700 EC 3 x 16 A RLI 900 FC 3 x 16 A RLI 1200 FC 3 x 25 A RLI 1200 EC 3...

Страница 16: ...nit s control system with which it works This can be checked under the menu point for con trol unit parameter P 1 Now press button B and the control unit will change to input mode Now you can use the...

Страница 17: ...res Pressure loss at the filter Hours of operation Filter change counter Control unit inputs Control unit outputs Fan stage 1 Supply air fan Fan stage 1 Extract air fan Fan stage 2 Fan stage 3 Fan sta...

Страница 18: ...te If the time 0 00 is given in the parameters the unit will not switch on or off If for example you do not want the unit to come on at the weekend you should set the value to 0 00 for Day 6 and Day 7...

Страница 19: ...0 OUT 21 0 IN 21 0 22 0 SUPPLY AIR 200 PA EXTRACT AIR 300 PA 9 3 2 Operating variables Menu You move to the operating variables menu by pressing the ON OFF button which must be held down for approx 3...

Страница 20: ...parameter Menu You can get to the menu for the supply and extract air parameters by pressing the ON OFF button for approximately 5 s The display then changes to the supply air fan The individual menu...

Страница 21: ...the contact is open the display will show NOT ENABLE The contact should be closed and then acknowledged with button B The default mode is AUTOMATIC P 5 Room supply or extract air temperature regulatio...

Страница 22: ...ing 9 4 Functions P10 EXHAUST AIR FI 250 Pa P11 CALIBRATE FILTER P12 AIR INPUT FIL 450 Pa P13 EXHAUST AIR FIL 320 Pa P10 Extract air filter pressure loss Setting for pressure loss at the supply air fi...

Страница 23: ...any unbalance or reduction in output Do not use aggressive or easily flammable products for cleaning impellers housing Preferably only water not flowing water or mild suds should be used The impeller...

Страница 24: ...Fig 12 Remove the defective drive belt and replace it with a new one Note see Technical Data Sec tion 14 for the length of drive belt according to type of device Place the new round belt on the drum...

Страница 25: ...y Display after changing the battery 21 0 1 0 8 0 21 0 1 0 8 0 10 3 2 Air filter Fig 17 1 Air filter supply air F7 Fig 18 2 Guide rail for air filter Fig 19 3 Air filter extract air M5 The differentia...

Страница 26: ...ically and purposefully when troubleshooting even when under the pressure of time In the worst case randomly and indiscriminately dismantling and changing settings may result in it no longer being pos...

Страница 27: ...the min supply air temperature is set under the parameters P 1 Possibly adjust parameter P 1 After removing the cause of the fault the fault must be acknowledged with button B Excess temperature supp...

Страница 28: ...x Cooling coil cold water x x x x x x Cooling DX Coil x x x x x x Diameter RHE mm 700 700 900 Length driving belt mm 2350 2350 2990 Specifications Units Model RLI 1200 FC 10 RLI 1200 FC 11 RLI 1200 F...

Страница 29: ...827 120813 120811 120838 120835 120837 120836 Length L mm 1405 770 770 Width B mm 1813 2213 2213 Height H mm 1795 2220 2220 Nominal width NW mm 1200x600 1200x650 1400x710 1400x710 Weight kg 1000 0 Ope...

Страница 30: ...ternal release AUTOMATED AUTOMATED ACKNOWLEDGED P 4 Selection of heating system HEATING HEATING COOLING HEATING COOLING DIRECT EVAPORATO P 5 Room or supply air temperature control ROOMTEMP CONTROL ROO...

Страница 31: ...English www ruck eu 31 15 2 Wiring diagrams RLI 700 FC Wiring diagrams No 119820 Part 1...

Страница 32: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 32 RLI 700 FC Wiring diagrams No 119820 Part 3 RLI 700 FC Wiring diagrams No 119820 Part 2...

Страница 33: ...English www ruck eu 33 RLI 700 FC Wiring diagrams No 119820 Part 4 RLI 700 FC Wiring diagrams No 119820 Part 5...

Страница 34: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 34 RLI 700 EC Wiring diagrams No 123344 Part 1 RLI 700 EC Wiring diagrams No 123344 Part 2...

Страница 35: ...English www ruck eu 35 RLI 700 EC Wiring diagrams No 123344 Part 2...

Страница 36: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 36 RLI 900 FC Wiring diagrams No 118155 Part 1...

Страница 37: ...English www ruck eu 37 RLI 900 FC Wiring diagrams No 118155 Part 2 RLI 900 FC Wiring diagrams No 118155 Part 3...

Страница 38: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 38 RLI 900 FC Wiring diagrams No 118155 Part 4 RLI 900 FC Wiring diagrams No 118155 Part 5...

Страница 39: ...English www ruck eu 39 RLI 1200 FC Wiring diagrams No 119819 Part 1...

Страница 40: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 40 RLI 1200 FC Wiring diagrams No 119819 Part 3 RLI 1200 FC Wiring diagrams No 119819 Part 2...

Страница 41: ...English www ruck eu 41 RLI 1200 FC Wiring diagrams No 119819 Part 4 RLI 1200 FC Wiring diagrams No 119819 Part 5...

Страница 42: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 42 RLI 1200 EC Wiring diagrams No 120618 Part 1...

Страница 43: ...English www ruck eu 43 RLI 1200 EC Wiring diagrams No 120618 Part 2 RLI 1200 EC Wiring diagrams No 120618 Part 3...

Страница 44: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 44 RLI 1200 EC Wiring diagrams No 120618 Part 4...

Страница 45: ...English www ruck eu 45 RLI 1600 FC Wiring diagrams No 120619 Part 1...

Страница 46: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 46 RLI 1600 FC Wiring diagrams No 120619 Part 2 RLI 1600 FC Wiring diagrams No 120619 Part 3...

Страница 47: ...English www ruck eu 47 RLI 1600 FC Wiring diagrams No 120619 Part 4 RLI 1600 FC Wiring diagrams No 120619 Part 5...

Страница 48: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 48 RLI 1600 EC Wiring diagrams No 120622 Part 1...

Страница 49: ...English www ruck eu 49 RLI 1600 EC Wiring diagrams No 120622 Part 2 RLI 1600 EC Wiring diagrams No 120622 Part 3...

Страница 50: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 50 RLI 1600 EC Wiring diagrams No 120622 Part 4...

Страница 51: ...English www ruck eu 51 RLI 2000 FC Wiring diagrams No 120625 Part 1...

Страница 52: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 52 RLI 2000 FC Wiring diagrams No 120625 Part 2 RLI 2000 FC Wiring diagrams No 120625 Part 3...

Страница 53: ...English www ruck eu 53 RLI 2000 FC Wiring diagrams No 120625 Part 4 RLI 2000 FC Wiring diagrams No 120625 Part 5...

Страница 54: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 54 RLI 2000 EC Wiring diagrams No 120626 Part 1...

Страница 55: ...English www ruck eu 55 RLI 2000 EC Wiring diagrams No 120626 Part 2 RLI 2000 EC Wiring diagrams No 120626 Part 3...

Страница 56: ...English Tel 49 7930 9211 0 Fax 49 7930 9211 150 56 RLI 2000 EC Wiring diagrams No 120626 Part 4...

Страница 57: ...English www ruck eu 57 Notes...

Страница 58: ...nts concerning a certain condition or suitability for a certain ap plication can be derived from our information The information given does not release the user from the obligation of own judgment and...

Отзывы: