Electrical installation may only be performed by qualified electricians in accordance with the installation
and operating manual and the national regulations, standards and guidelines in force:
•
ISO, EN, DIN and VDE specifications, including all safety requirements.
•
Technical connection conditions
•
Safety at work and accident prevention requirements.
•
This list does not claim to be complete.
Requirements should be applied under one‘s own personal responsibility.
The following points should be noted and followed:
•
The electrical connections must be made as shown in the corresponding wiring diagrams and terminal
diagrams.
•
The type of cable, size of cable and method of laying should be determined by an authorized electri
-
cian.
•
Low and extra-low voltage cables should be laid separately.
•
An all-pole mains disconnection device with at least 3 mm contact gap must be provided in the supply
line.
•
Use a separate cable inlet for each cable.
•
Any cable inlets that are not used must be sealed so that it is airtight.
•
All cable inlets must have strain relief.
•
Create equipotential bonding between the unit and the duct system.
•
Check all protective measures after the electrical connection work (earthing resistance, etc.).
•
Electricity warning (hazardous voltage)
»
Failure to observe the hazard may result in death, injury or damage to property.
→
Before performing any work on conductive parts, always disconnect the unit completely from the
electricity supply and make sure that it cannot be switched back on again.
6.1. Permitted installation positions
Abb. 6b:
Ceiling installation
Abb. 6c:
Wall installation, air
flowing upwards.
Abb. 6a:
Wall installation, connec-
tions upwards.
7. Electrical connection
6.2. Operating limits
Operating limits indoor installation
Fresh air temperature
-28 °C to +40 °C
Installation place:
+5 °C / max. 15g/kg Water content of the air
For the ventilation of rooms where the emission sources are human metabolism or building materials
and structures, such as offices, spaces for public services, meeting rooms.