Integer Input and Integer Output Point Groups
Note:
The total number of point groups configured in each MODBUS card must be less
or equal to 64.
Point Group
Adding an Integer Input Point Group or Integer Output Point Group to the node creates 16 Integer Raw Count
I/O points.
Start Address
A start address for the Point Group must be entered here to create a contiguous MODBUS message exchange
within the controller node.
Inter Scan Delay (ms)
The Inter Scan Delay defines the scan rate, in terms of a minimum delay between accesses in milliseconds.
For example, if the delay is 100, the point group will not be scanned until 100 milliseconds have elapsed since
the last time it was scanned.