Einbau- und Betriebsanleitung
Installation and Operating instructions
SR3300-8010
SR-3300
Page 54
07/2018
7.2
Warning code
Warning Code
Description
Action
B
➢
Pv Span
–
Pv Zero range is below 500.
➢
The angle of feedback lever is too small.
➢
Re-install the positioner.
➢
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
➢
After re-installation, perform AUTO1.
F
➢
Full open/close elapsed time is less than 1
second.
➢
Actuator size is too small.
➢
Use variable orifice.
➢
Use larger actuator.
G
➢
Pv is below 100.
➢
The angle of feedback lever is too large.
➢
Re-install the positioner.
➢
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
➢
After re-installation, perform AUTO1
H
➢
Pv is over 4000.
➢
The angle of feedback lever is too large.
➢
Re-install the positioner.
➢
Ensure the feedback lever does not touch the
lever stopper at 0% and 100%.
➢
After re-installation, perform AUTO1