Parameter Mode (PARAM)
AUTO CAL optimizes most of the valve actuator control values. However, in some instances, hunting or oscillation may occur
when the valve actuator control values are not optimized. Hunting or oscillation can be prevented by adjusting parameter
values.
Once parameter values have been changed, the changed values are being affected as soon as you save the value. To
save the changes, please ensure to press “ENTER” button. There is no need to go back to “RUN” mode after changes
are being made to observe the changes.
6.3.3.1
Dead-Zone (dEAdZONE)
Dead-Zone indicates the percentage of error allowance. In case of high level of packing friction, which may cause hunting,
6.3.3.2
P value (KP)
P value indicates the ratio of the compensation signal based on the percentage of error allowance. As the value increase, the
positioner finds the target value quickly, but it is more likely to have hunting.
⇨