Troubleshooting RSLinx and RSLogix Comms
When attempting to configure the 515RTAENI in
RSLinx I see “unrecognized device” and a yellow
question mark. Why do I see this?
In RSLinx, when using EtherNet/IP, the EDS file for
the 515RTAENI must be installed for RSLinx to
recognize the device type. RTA recommends that
you use the Ethernet driver.
Using RSLinx , pg. 41
When attempting to configure the RSLogix
Controller Communications Comms Path, why
do
I get a 0x10 error after clicking the “Apply”
button.
The 0x10 error indicates that either the serial
baud rates do not match or there is an issue with
the serial cable
Verify
that the serial baud rate configured in the
515RTAENI is the same baud rate configured in
the controller
document located on CD pg. 20)
, also verify that
the serial cable is the correct cable and is properly
connected.
Why are the LEDs flashing red when connected
to the 515RTAENI using RSLinx/RSLogix?
Please reference pg. 35
for the LED behavior.