Real Time Automation, Inc.
11
1-800-249-1612
Pinouts & Wiring
Pinouts
The gateway has two connectors for communication: T-Strip (Port 0) and DB9 port (Port 1). Either port
can be used for RS-232 communications using the pinouts in the diagram below.
DB9 pinouts are as follows:
Pin 2
–
RX
Pin 3
–
TX
Pin 5
–
GND
CABLE INFORMATION:
Wiring
It is recommended to use the following programming cables:
•
1761-CBL-PM02
o
https://www.rtautomation.com/product/generic-micrologix-programming-cable/
•
CBL-FF-6
o
https://www.rtautomation.com/product/null-modem-cable/
•
1784-CP10
o
https://www.rtautomation.com/product/1784-cbl/
IMPORTANT:
The 1761-CBL-PM02 Ser. C when used with a SLC5/04 has a different pin out and will
cause 515RTAENI hardware failure. Any 1761-CBL-PM02 cable is only to be used for MicroLogix PLCs.
It is highly recommended to follow wiring recommendations regarding the Allen-Bradley serial cables.
Failure to do so may result in poor or inoperable intermittent communications.
NOTE:
Only one physical port can be used at a time.
Содержание 515RTAENI
Страница 29: ...Real Time Automation Inc 29 1 800 249 1612...