Real Time Automation, Inc.
39
1-800-249-1612
249
Email address. The 2nd element is the length of the email address and the 3rd is the email
address. The “ST15:0” is a file and offset in the target Ethernet device. That will, of course,
vary by device.
ST15:0 17
250
A controller write to node 250 can assign IP address settings to the 515RTAENI.
Function
Data Type
Operation
IP
Address
Integer
4 words
Format aaa.bbb.ccc.ddd (decimal).
First octet is between 1-223, not 127
First octet is not 169.254 or 169.255
0.0.0.0 returns an error
Subnet
Mask
Integer
4 words
Class A address (First octet is 1 to 126) 255.0.0.0
Class B address (First octet is 128 to 191) 255.255.0.0
Class C address (First octet is 192 to 223)
255.255.255.0
Gateway
Integer
4 words
Only needed if there is a Default Gateway on the
network.
Security
Mask 1
Integer
4 words
Default is set to 000.000.000.000
Security
Mask 2
Default is set to 000.000.000.000
251
515RTAENI f
rom email address. Messages sent will have this “From” address.
252
●
BootP Initially (
Unsupported by RTAENI
, will default to DHCP)
●
BootP Fallback (
Unsupported by RTAENI
, will default to DHCP)
●
BootP Always (
Unsupported by RTAENI
, will default to DHCP)
●
DHCP Only
Offset
Operation
1
Use static IP address
4
Use DHCP to acquire IP address